testo 550 Digital Manifold
with Bluetooth/App
Temperature port on each side
2 line, back lit LCD display
Control keys
Pressure zeroing
Escape Key
3 x 1/4” SAE connections
Show Min/Max/Mean values
Valve knobs
Min, Max and Mean
Warranty
Troubleshoot,
evacuate, charge
AC, heat pump or
auto mode
Conduct leak test
The testo 550 has a two year warranty. If registered, the warranty is extended to 5 years.
Pic. 16
Arrow keys
Power On/Off
Backlight
Bluetooth Activation
The testo 550 now comes standard with Bluetooth.
1. First turn on the testo Refrigeration App on
your smart device.
2. Once the app is running, turn on the testo
550.
3. Press and hold the UP and DOWN arrow
simultaneously to activate Bluetooth.
4. The Bluetooth icon will flash to the left of the
battery display icon and remain on once
bluetooth is activated. (Pic. 16)
5. The app will now show your 550 as an
available device. (Pic 17)
6. Select your instrument in the app to pair your
device.
Pic. 17
The testo 550 offers the ability to display Min, Max
and Mean measurement values.
1. Simply press the Min/Max Mean button to cycle
this setting.
2. Pressing this button once will display the Min
setting.
3. Pressing the button twice will display the Max
setting.
4. Pressing the button three times will display the
Mean setting.
5. Pressing the button a fourth time will return the
setting to the standard measurement display
Changing the batteries
Testo 550 uses 4x 1.5 V, AA batteries.To
replace the batteries please follow these
few steps below:
1. Fold out the hook (Pic. 1).
2. Grab the clip and squeeze it
together and remove the cap (Pic.
2).
3. Insert/Change the batteries.
Observe the polarity.
Power ON / OFF
1. Connect probes to the testo 550 prior
to powering it up.
2. Press the power button [ ] to turn
the testo 550 on.
3. All display segments will light up for
2 seconds.
4. Measurement view is then displayed
5. Press and hold the power button to
turn the testo 550 off.
Choose the refrigerant
Set the Units / Altitude / Mode
1. Press the [Set] button once to get to the
temperature units menu (Pic. 4). Choose
the required units with the arrow keys.
3. Press the [Set] button again to view the
pressure units (Pic. 5). Choose the desired
units with the arrow keys.
4. Press the [Set] button again to select
absolute or relative pressure (Pic. 6)
5. Press[Set] again so that you can set the
barometic pressure in
inHg (Pic. 7) .
6. Press the [Set] button again to select the
AC/R [ ], heat pump [ ], or Auto [ ].(Pic
8). Auto mode senses if the Low pressure
side is 15 psi higher than the High pressure
side, and will automatically reserve the
display of the High / Low side pressures
7. Press the [Set] button again to set the
Auto Off Feature. Setting this On will allow
the 550 to power down automatically when
not in use.
8. Press [Set] a final time to turn the Tfac
on or off using the arrow keys. (Pic. 9)
9. Press the [Esc] button to exit the settings
menu.
Backlight
Testo 550 has a backlight to
improve viewing in dark or
daylight conditions. Press the
backlight button to turn the
backlight on. Press it once again
to turn the backlight off.
Pressure zeroing
The pressure sensors should be zeroed before each
use.
1. Loosen the hose connections
2. Open the valve knobs to confirm that there is
no pressure in the manifold
3. Press the [p=0] button and the sensors will
display zero pressure.
Leak Test
The temperature compensated leak test is used to
indicate leaks in an AC/R or heat pump system.
1. Plug in the temperature probe into the high side of
the instrument.
2. Press the set button 6 times to reach the Tfac setting.
Press the UP arrow to cycle this setting to OFF.
Press SET to select this setting
3. Zero the pressure sensors.
4. Connect the testo 550 to the system.
5. Press the [Mode] button once to get to the leak test
mode (Pic. 14).
6. Now press the [R, Start/Stop] button to start the
test. (Pic. 15).
7. The test duration depends on the system size.
8. Press [R, Start/Stop] again to stop the test.
9. The results will be displayed.
10. Press the [Mode] button twice to return to the
normal measurement mode. Please make sure to
repeat step 2 to turn the Tfac back to ON before
starting normal testing again.
Note: rP could be different from the
starting and final test pressure rP as the
true rp is calculated from the gas laws.
Pic. 15
Pic. 14
Pic. 13
Pic. 12
Pic. 11
Pic. 10
Pic. 7
Pic. 6
Pic. 5
Pic. 4
Pic. 3
Pic. 2Pic. 1
Pic. 8
Superheat and Sub-cooling
The testo 550 calculates superheat and sub-cooling in
real time.
1. Connect the temperature probes and hoses to the 550.
2. Turn on the instrument.
2. Connect the testo 550 and the pipe clamp probes to
the air conditioning, refrigeration or heat pump system.
3. You will now see the calculated evaporation and
condensation temperature (Ev and Co) and system
pressures at the top of the display. (Pic. 10)
4. Press the UP-arrow once to see the temperature
difference (Pic. 11)
5. Press the UP-arrow twice to see the real time
superheat and sub-cool (SH and SC) (Pic. 12).
6. Press the UP-arrow for the third time to see the real
time measured temperature (T1 and T2) (Pic. 13).
7. Press the UP-arrow again to get back to the calculated
evaporation and condensation temperature. You can
also use the DOWN-arrow to switch between the menus
but the order will be reversed.
1. Press the [R, Start/Stop] button to bring
up the refrigerant selection screen (Pic. 3).
2. Use the arrow keys to scroll through the
refrigerant choices.
3. Press the [R, Start/Stop] button to set the
desired refrigerant.
Pic. 9