www.crouse-hinds.com US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright
©
2022 Eaton
776
2E
2E
AWhen terminal blocks or approved Class I, Division 2 devices are installed within the enclosure in accordance with NEC/CEC requirements. These enclosures are NOT explosionproof
and will NOT contain an explosion. Installation of arcing and sparking devices which are not Class I, Division 2 rated or higher is NOT PERMITTED.
BEnclosures with gland plates are limited to -40°C.
CPainted mild steel not available with ATEX or IECEx rating.
*Painted versions only available on demand.
Applications:
• Designed to meet the requirement for
distribution and lighting junction boxes
• Available in 13 sizes with standard
finishes of painted or 316L stainless
steel, together with the high IP rating,
make these enclosures suitable for all
environmental conditions
• Stainless steel versions are particularly
recommended for use in marine or other
corrosive environments
Technical specifications:
Description Specification
Material
1.5mm thick stainless steel grades: 316L (1.4401); 304 (1.4301)
or painted mild steelC (optional)
Finish
Stainless steel
Painted
Corrosion-resistant electro-polished surface
RAL 7032 (gray)
Gasket Foam-in-place silicone (standard); cut silicone (with gland plates)
Cover mounting 4 x M6 slotted, hexagon head captive screws
Grounding
STB121208-303020
STB383822-604022
M6 internal/external ground stud
M10 internal/external ground stud
Box mounting
STB121208-252512
STB163812-303020
STB383822-604022
2 x external lugs, 0.315” (8mm) clearance holes
4 x external lugs, 0.315” (8mm) clearance holes
4 x external lugs, 0.433” (11mm) clearance holes
Equipment mounting
Mounting pillars or TAS 20 rails welded to base of enclosure
(see Dimensions for details)
Ingress protection All types IEC/EN 60529, IP66
Service temperature
range
No gland plates
With gland plates
-55°C to +120°C
-40°C to +120°C
Impact resistance Minimum 7 J (Nm) to IEC/EN 60079-0, IK 10
Gland plates STB383822-604022
Optional 3mm thick gland plates available in bottom, left, top
and right configurations
Certifications and
compliances:
S-TB enclosures
Cl. I, Div. 2, Groups A, B, C, DA
NEMA Type 3S, 4 (painted steel*)
NEMA Type 4X (stainless steel)
NEMA Type 6
IP66
IECEx/ATEX
TR-CU/EAC
• Class I, Division 2, Groups A, B, C, DA
• cULus to UL50/C22.2 No. 94-M91
• NEMA Type 3S, 4 (painted steel*), NEMA
Type 4X (stainless steel), NEMA Type 6;
IP66
• UL Listed E115376 (Ordinary Location)
• IECEx and ATEX component certificate
– BVS13ATEXE015U and IECEx BVS
13.0025U
• 2G Ex eb IIC Gb or 2D Ex tb IIIC Db
• TR-CU and EAC certified
S-TB-T terminal boxes:
S-TB enclosures are available assembled
as custom configured and certified terminal
boxes. Options include custom entries,
cable glands and plugs with built-in terminals
(Ex-e and Ex-i) and other equipment.
Contact factory for ordering details.
Standards:
• IEC/EN 60079-0
• IEC/EN 60079-7
• IEC/EN 60079-31
• IEC/EN 60529
Certificates:
• BVS16 ATEX-E-096X
• IECEx BVS 16.0062X
• RU_C-DE.AA87.B.00885
Ambient temperatures:
• -55B/-40°C up to +40°C (T6 and maximum
surface temperature of T80°C)
• -55B/-40°C up to +55°C (T5 and maximum
surface temperature of T95°C)
• -55B/-40°C up to +65/70/80/100/110°C
(with temperature class T4 and maximum
surface temperature of T120°C)
Materials:
• Equipment available in 316L stainless
steel enclosures
Electrical ratings:
• Rated voltage up to 690V AC/DC; rated
current up to 400A; conductor cross-
sections up to 240mm
2
Note: Ambient temperature range depends on ratings of
built-in components.
Markings:
• ATEX and IECEx: Ex eb IIC T6/5/4 Gb;
Ex tb IIIC T80/95/120°C Db or Ex tb IIIC
T80/95/120°C
• EAC CU TR: 1Ex e IIC T6/T5 Gb X or Ex tb
IIIC T80/95/120°C Db X
• NEC 500: Class I, Division 2, Groups A, B,
C, DA