www.crouse-hinds.com US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright
©
2022 Eaton
776
2E
2E
AWhen terminal blocks or approved Class I, Division 2 devices are installed within the enclosure in accordance with NEC/CEC requirements. These enclosures are NOT explosionproof
and will NOT contain an explosion. Installation of arcing and sparking devices which are not Class I, Division 2 rated or higher is NOT PERMITTED.
BEnclosures with gland plates are limited to -40°C.
CPainted mild steel not available with ATEX or IECEx rating.
*Painted versions only available on demand.
Applications:
Designed to meet the requirement for
distribution and lighting junction boxes
Available in 13 sizes with standard
finishes of painted or 316L stainless
steel, together with the high IP rating,
make these enclosures suitable for all
environmental conditions
Stainless steel versions are particularly
recommended for use in marine or other
corrosive environments
Technical specifications:
Description Specification
Material
1.5mm thick stainless steel grades: 316L (1.4401); 304 (1.4301)
or painted mild steelC (optional)
Finish
Stainless steel
Painted
Corrosion-resistant electro-polished surface
RAL 7032 (gray)
Gasket Foam-in-place silicone (standard); cut silicone (with gland plates)
Cover mounting 4 x M6 slotted, hexagon head captive screws
Grounding
STB121208-303020
STB383822-604022
M6 internal/external ground stud
M10 internal/external ground stud
Box mounting
STB121208-252512
STB163812-303020
STB383822-604022
2 x external lugs, 0.315” (8mm) clearance holes
4 x external lugs, 0.315” (8mm) clearance holes
4 x external lugs, 0.433” (11mm) clearance holes
Equipment mounting
Mounting pillars or TAS 20 rails welded to base of enclosure
(see Dimensions for details)
Ingress protection All types IEC/EN 60529, IP66
Service temperature
range
No gland plates
With gland plates
-55°C to +120°C
-40°C to +120°C
Impact resistance Minimum 7 J (Nm) to IEC/EN 60079-0, IK 10
Gland plates STB383822-604022
Optional 3mm thick gland plates available in bottom, left, top
and right configurations
Certifications and
compliances:
S-TB enclosures
Cl. I, Div. 2, Groups A, B, C, DA
NEMA Type 3S, 4 (painted steel*)
NEMA Type 4X (stainless steel)
NEMA Type 6
IP66
IECEx/ATEX
TR-CU/EAC
Class I, Division 2, Groups A, B, C, DA
cULus to UL50/C22.2 No. 94-M91
NEMA Type 3S, 4 (painted steel*), NEMA
Type 4X (stainless steel), NEMA Type 6;
IP66
UL Listed E115376 (Ordinary Location)
IECEx and ATEX component certificate
– BVS13ATEXE015U and IECEx BVS
13.0025U
2G Ex eb IIC Gb or 2D Ex tb IIIC Db
TR-CU and EAC certified
S-TB-T terminal boxes:
S-TB enclosures are available assembled
as custom configured and certified terminal
boxes. Options include custom entries,
cable glands and plugs with built-in terminals
(Ex-e and Ex-i) and other equipment.
Contact factory for ordering details.
Standards:
IEC/EN 60079-0
IEC/EN 60079-7
IEC/EN 60079-31
IEC/EN 60529
Certificates:
BVS16 ATEX-E-096X
IECEx BVS 16.0062X
• RU_C-DE.AA87.B.00885
Ambient temperatures:
• -55B/-40°C up to +40°C (T6 and maximum
surface temperature of T80°C)
• -55B/-40°C up to +55°C (T5 and maximum
surface temperature of T95°C)
• -55B/-40°C up to +65/70/80/100/110°C
(with temperature class T4 and maximum
surface temperature of T120°C)
Materials:
Equipment available in 316L stainless
steel enclosures
Electrical ratings:
Rated voltage up to 690V AC/DC; rated
current up to 400A; conductor cross-
sections up to 240mm
2
Note: Ambient temperature range depends on ratings of
built-in components.
Markings:
ATEX and IECEx: Ex eb IIC T6/5/4 Gb;
Ex tb IIIC T80/95/120°C Db or Ex tb IIIC
T80/95/120°C
EAC CU TR: 1Ex e IIC T6/T5 Gb X or Ex tb
IIIC T80/95/120°C Db X
NEC 500: Class I, Division 2, Groups A, B,
C, DA
www.crouse-hinds.com US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright
©
2022 Eaton
777
2E
2E
STB S1 25 25 12
Ordering information:
Part number example
STBS1252512
Material
S1
Polished 316L stainless
steel (standard)
S2
Polished 304 stainless
steel
P1
Decorative painted 316L
stainless steel*
PS
Painted mild steel*
Height
As per certified range options
Width
As per certified range options
Depth
As per certified range options
S-TB enclosures
Cl. I, Div. 2, Groups A, B, C, DD
NEMA Type 3S, 4 (painted steel*)
NEMA Type 4X (stainless steel)
NEMA Type 6
IP66
IECEx/ATEX
TR-CU/EAC
DWhen terminal blocks or approved Class I, Division 2 devices are installed within the enclosure in accordance with NEC/CEC requirements. These enclosures are NOT explosionproof
and will NOT contain an explosion. Installation of arcing and sparking devices which are not Class I, Division 2 rated or higher is NOT PERMITTED.
*Painted versions only available on demand.