1
PA-9 Series
Application Guide
TRIPPING BREAKERS
Tripping Breakers can be a nuisance problem that can cause
sags, power interruptions and industries to go off line. Current
swells, voltage swells or transients are the most common cause of
tripping breakers. First or second generation solid-state tripping
devices on low-voltage circuit breakers use to respond to peak
currents. Since about 1978, these devices have been responding to
RMS current values. Therefore, earlier models may cause nuisance
tripping in circuits carrying harmonic currents.
Common Causes of current swells can include in-rush current
or load switching.
Common Causes of voltage swells can include load switching or
utility faults.
Common Causes of transients can include lightning strikes or
capacitor bank switching.
Below is an example of an RMS Current and Voltage swell.
PA-9 Configuration
Feature Status Notes
Enable Power Calculations Enable (Select correct configuration)
Enable RMS Recording Enable
MIN, RMS and MAX MIN, RMS and MAX
Clock Hour Orientation Enabled
Enable Flicker Recording Disabled
Hysteresis 2%
Sags Enabled
Sag Limit See Below
Swells Enabled
Swell Limit See Below
Sub-cycle Enabled
Sub-Cycle Limit See Below
THD Limit Enable Voltage Only
THD Limit See below
Enable Waveform Capture Enabled
Waveform Trigger Event Trigger
Pre-Triggers 2
This configuration is designed
to capture out of limit events.
It focuses on sub-cycle, sag,
swell and THD events.
In this configuration the
waveform capture is set to
Exceedance. This will allow
the unit to capture a
waveform every time there is
an out of limit event. By
analyzing the waveforms
associated with transients one
can determine whether the
transient is due to lightning or
capacitor switching.
Also note that waveform limit
is enabled and set to 200. This
will limit the number of
waveforms captured to 200.
This is done so that the unit’s
memory does not fill
PA-9
Application Guide
UK
Archcliffe Road, Dover
CT17 9EN England
T (0) 1 304 502101
F (0) 1 304 207342
UNITED STATES
4271 Bronze Way
Dallas, TX 75237-1018 USA
T 1 800 723 2861
T 1 214 333 3201
F 1 214 331 7399
OTHER TECHNICAL SALES OFFICES
Norristown USA, Toronto CANADA,
Mumbai INDIA, Paris FRANCE, Sidney
AUSTRALIA,
Guadalajara SPAIN and
The Kingdom of BAHRAIN.
ISO STATEMENT
Registered to ISO 9001:1994 Reg no. Q 09250
Registered to ISO 14001 Reg no. EMS 61597
PA9_18_AG_En_V02
www.megger.com
Megger is a registered trademark
2
Feature Status Notes
Post Triggers 5 - 10
Waveform Limit Enabled
Expected Number of Events 300
Memory Mode Stop When Full
Default Frequency 50 or 60Hz as Required
Enable Frequency Recording Enabled
MIN, AVG, MAX AVG
prematurely in the case of a
large amount of events in a
small period of time.
IEEE Recommendations: For a 120V / 60Hz Load
per IEEE1159.
Sag Limit = 108V (10% of Nominal)
Voltage Swell Limit = 126V (5% of Nominal)
Current Swell Limit = Dependant on Breaker Trip point
Sub-cycle = 200V (Approx 2 times Phase to Neutral)
Voltage Imbalance = +/- 2%
Voltage THD = 20% for small customers, 5% for large customers
Frequency Limit = +/- 1Hz
European Recommendations: For a 230V / 50Hz Load
per EN50160.
Sag Limit = 207V (10% of Nominal)
Swell Limit = 253V (10% of Nominal)
Current Swell Limit = Dependant on Breaker Trip point
Sub-cycle = None Provided
Voltage Imbalance = +/-2%
Voltage THD Limit = 8%
Frequency Limit = +/- 1Hz
NOTE: If equipment is tripping out due to over voltages it may
be advantageous to set the sub-cycle limit to approximately 25% of
nominal. (Often sensitive electronic equipment will trip out at
transient over-voltages of no more than 115-120% of nominal.)
Visit our web site at: www.megger.com