3-349-607-03
13/8.14
GMC-I Messtechnik GmbH
METRISOG500/G1000/G500MM
High-Precision
Insulation, Low Resistance and Voltage Measurement Instrument
DAkkS Calibration Certificate as Standard Feature
German
Accreditation Body
D-K-15080-01-01
Applications
METRISO G500/G1000 as well as METRISO G500MM insulation and
resistance measuring instruments allow for quick and effective
testing of protective measures in accordance with DIN VDE 0100,
ÖVE-EN 1 (Austria),
NIV/NIN SEV 1000
(Switzerland), and regula-
tions specific to other countries as well. The instruments are
equipped with a microprocessor and comply with IEC/EN 61557
/ VDE 0413 regulations:
Part 1: General requirements
Part 2: Insulation resistance measuring instruments
Part 4: Instruments for measuring resistance at earthing conduc-
tors, protective conductors and equipotential bonding
Part 10: Combined measuring equipment for testing, measuring
or monitoring protective measures
As well as requirements per VDE 0701-0702:
Repair, modification and testing of electrical devices
The insulation measuring instruments are suitable for the following
tasks:
Measurement of insulation resistance at voltage-free
devices and systems, up to 1000 V depending upon variant
Testing of the resistance of earthing conductors, protective
conductors and equipotential bonding
Checking of test objects for absence of voltage
Testing of electrostatic discharge capacity at floor coverings
(using shielded measurement cables) – EN 1081
Features Overview of Both Instrument Variants
METRISO G1000 G500 G500MM
Article number M550C M550D M550K
Measurements
RISO U = 1000 V
——
RISO U = 50, 100, 250, 500 V
✓✓✓
R 10 ... 10 k
✓✓✓
RLO 0.01 ... 10
✓✓
U 0 ... 1000 V
——
U 0 ... 500 V
✓✓✓
Display Functions
Backlit display
✓✓✓
Limit value LED (green/red) for:
Additional acoustic signal, limit value per VDE 0100
R
ISO
R
LO
R
ISO
R
LO
R
ISO
LED for dangerous contact voltage
(when switched off)
✓✓
LCD symbol for external voltage
✓✓✓
Battery level display
✓✓✓
Special Functions
Discharge capacitive devices under test
✓✓✓
Safety shutdown (UBatt < 8 V)
✓✓✓
Features
Measuring categories CAT II 1000 V /
CAT III 600 V / CAT IV 300 V
——
Measuring category CAT III 600 V / CAT IV 300 V
✓✓✓
10 M test resistor
✓✓
DAkkS calibration certificate
✓✓✓
Insulation measurement per EN 61557-2/VDE 0413, part 2
Digital and analog display, backlit
Indication of dangerous contact voltage LED
Acoustic signalling when limit value is exceeded
Detection of interference voltage in switch position OFF*
Overvoltage protection
Protects the instrument in the event of inadvertent connection
to mains power
Fuse link for all resistance measuring ranges
New Electronic fuse* for the protection of low resistance
and resistance measurement R
LO
and R
Compact and rugged for service calls under harsh conditions
METRISO G1000: Voltage testing and measurement up to 1000 V
METRISO G500/G1000:
Intelligent filter: precise and measurement-dependent
activation for the measurement of very high resistances
Low-resistance measurement per EN 61557-4/VDE 0413, part 4
One measuring point self-test with test resistance of 10 M
per IEC/HD 60364-6 / EN 50110
* not METRISO G500MM (M550K)
METRISOG500/G1000/G500MM
High-Precision
Insulation, Low Resistance and Voltage Measurement Instrument
2 GMC-I Messtechnik GmbH
Characteristic Values
1)
Display range up to 600 V
2)
Display range up to 1.2 kV
3)
the indicated accuracy is only achieved with the shielded high-resistance
measuring cable KS-C (article no. Z541F)“
4)
does not conform to DIN EN 61557-2
5)
up to 5
Voltage at Device Under Test During Insulation Resistance Measurement
Measuring voltage Ux at the device under test depending upon its resistance Rx at nominal voltages of 100, 250, 500 and 1000 V:
Intelligent Filter
Measurement-dependent and precise activation for the measurement of very high resistances with:
beating, i. e. compensation of 16
2
/
3
Hz and 50 Hz interference
attenuation of capacitive influences from power cables, etc.
suppression of electric field influences
Meas.
Qty.
UiSO Range Measuring Range
Reso-
lution
Open-Circuit
Voltage
U
0max
Test
Current
Intrinsic Uncertainty
Measuring
Uncertainty
Overload
Capacity
RISO
50 V
100 V
G500(MM): 250 V / 500 V
G1000: 250 V / 500 V / 1000 V
100 k 10.0 k ... 99.9 k 0.1 k
50 V /100 V:
1.25 U
ISO
250 V /
500 V /
1000 V:
1.1 U
ISO
I
N
= 1 mA
I
K
5 mA
(5% rdg. + 3 d) (7% rdg. + 3 d)
METRISO G500(MM)
:
600 V AC/DC
TRMS
METRISO G1000:
1000 V AC/DC
TRMS
1 M 100 k ... 999 k 1 k
10 M 1.00 M ... 9.99 M 10 k
100 M 10.0 M ... 99.9 M 100 k
1 G 100 M ... 999 M 1 M
10 G 1.00 G ... 9.99 G 10 M
100 G 10.0 G ... 99.9 G 100 M (8% rdg. + 3 d)
3)
(10% rdg. + 3 d)
3)
200 G 100 G ... 199 G 1 G (25% rdg. + 5 d)
3)
(50% rdg. + 20 d)
3) 4)
U
AC/DC
METRISO G500
METRISO G500MM
100 V 10.0 V ... 99.9 V 0.1 V
(2.5% rdg. + 3 d) (5% rdg. + 3 d)
600 V AC/DC
TRMS
500 V 100 V ... 510 V
1)
1 V
METRISO G1000
100 V 10.0 V ... 99.9 V 0.1 V
(2.5% rdg. + 3 d) (5% rdg. + 3 d)
1000 V AC/DC
TRMS
1000 V 100 V ... 999 V
2)
1 V
RLO
METRISO G500
METRISO G1000
10 0.17 ... 9.99
0.01
4 V < U
0
< 6 V
200 mA I
I
260 mA
(2.5% rdg. + 3 d) (5% rdg. + 3 d)
METRISO G1000:
1000 V AC/DC TRMS
METRISO G500:
600 V AC/DC TRMS
R
Display range as of
01.0
100 10.0 ... 99.9 0.1
U
0
max. 15 V
1 mA I
I 1,3 mA
(2.5% rdg. + 3 d) (5% rdg. + 3 d)
METRISO G1000:
1000 V AC/DC TRMS
METRISO G500(MM)
:
600 V AC/DC TRMS
1 k 100 ... 999 1
10 k 1.00 ... 9.99 k 10
100
U
x
/V
R
x
/k
U
N
= 100 V
0
20
40
60
80
100
250
U
x
/V
R
x
/k
U
N
= 250 V
0
50
100
150
200
250
0
100
200
300
400
500
500
U
N
= 500 V
U
x
/V
R
x
/k
0
200
400
600
800
1000
1
U
N
= 1000 V
U
x
/V
R
x
/M