Series :GD20-0R7G-4
Nominal voltage :380VAC
Nominal power :0.75kW
Overload : Heavy Duty
Efficiency data for the Drive
Standby losses:
Relative
Torque / %
Relative
Speed / %
Losses
Relative losses
Drive Efficiency
100
50
25
0
10 20
50
90
Energy Efficiency Certificate
Drive efficiency according to IEC/EN 61800-9-2 (supersedes EN 50598-2)
Nominal current :2.5A
Nominal apparent power :1.65kVA
Nominal frequency :50Hz
Efficiency data for the Drive + motor (standard IE2 reference motor)
Efficiency data for the Drive
100
50
25
0
10 20
50
90
Relative
Torque / %
Losses
Relative losses
System Efficiency
38W
2.33%
88.09%
40W
2.4%
90.88%
44W
2.68%
94.28%
40W
2.42%
96.82%
34W
2.09%
80.78%
55W
3.34%
85.84%
35W
2.1%
93.04%
26W
1.55%
96.6%
48W
2.71%
76.51%
30W
1.8%
83.37%
188W
25.13%
/%
189W
25.20%
/%
205W
27.38%
/%
264W
35.16%
/%
103W
13.79%
/%
103W
13.72%
/%
125W
16.60%
/%
171W
22.86%
/%
82W
10.94%
/%
83W
11.10%
/%
23W
1.4%
92.47%
101W
13.50%
/%
12W
0.7%
96.94%
/W
/%
/%
Series :GD20-1R5G-4
Nominal voltage :380VAC
Nominal power :1.5kW
Overload :Heavy Duty
Efficiency data for the Drive
Standby losses:
Relative
Torque / %
Relative
Speed / %
Losses
Relative losses
Drive Efficiency
100
50
25
0
10 20
50
90
Energy Efficiency Certificate
Drive efficiency according to IEC/EN 61800-9-2 (supersedes EN 50598-2)
Nominal current :3.7A
Nominal apparent power :2.4kVA
Nominal frequency :50Hz
Efficiency data for the Drive + motor (standard IE2 reference motor)
Efficiency data for the Drive
100
50
25
0
10 20
50
90
Relative
Torque / %
Losses
Relative losses
System Efficiency
55W
2.29%
90.8%
57W
2.35%
92.9%
54W
2.24%
96.07%
53W
2.19%
97.52%
41W
1.7%
86.67%
38W
1.59%
90.35%
36W
1.46%
94.65%
28W
1.15%
97.23%
33W
1.39%
84.03%
32W
1.32%
88.79%
303W
20.19%
/%
304W
20.25%
/%
329W
21.94%
/%
431W
28.72%
/%
149W
9.9%
/%
147W
9.79%
/%
184W
12.26%
/%
250W
16.69%
/%
111W
7.39%
/%
110W
7.32%
/%
27W
1.11%
94.27%
141W
9.41%
/%
18W
0.74%
97.44%
/W
/%
/%