PS3500 Power Supply Backplane -
6-position
PS3500-TB-6
<
6-position backplane for PS2500/PS3500 series power modules
<
Multiple input/output wiring configurations
<
Removable terminals for easy wiring
<
Serial or parallel fault bus
<
ATEX, IECEx, and cULus approvals for Div 2/Zone 2
6 position N+1 Power Supply Backplane for use with PS2500 and PS3500 N+1 Power Supplies.
Function
The PS3500-TB-6 is a 6-position backplane used by the PS2500/PS3500 series power supply modules. Power configuration and alarms are
controlled by DIP switches on the backplane. The backplane connects to universal AC (90- 250 V) or DC (90-300 V) inputs and supports
redundancy.
The PS3500-TB-6 allows a maximum of 90 A of output power, 75 A in N+1 configuration or 45 A in triple redundant mode. Automatic load sharing
of all of the power modules is built into the backplane. Input and output lines can be wired independently or in parallel, providing easy
configuration of N+1 redundancy.
The fault bus can be configured in serial or parallel combinations.
Connection
90 - 250 V AC
90 - 300 V DC
24 V DC
Zone 2
Div. 2
Technical Data
Interface
Type diagnostic bus: RS 485
Input
Rated values terminal ratings: current 6.5 A per slot
Voltage 90 ... 250 V AC, 44 ... 66 Hz; 90 ... 300 V DC
Output
Rated values terminal ratings: current 65 A, voltage 300 V
Fault signal removable terminals : power module alarm
Indicators/settings
Control elements DIP switches for alarm and load sharing configuration
potentiometers for output voltage adjustment
Directive conformity
1
Release
date:
2022-02--
08 Date of
Release date: 2022-02-08 Date of issue: 2022-02-08 Filename: 911113_eng.pdf
Germany: +49 621 776 2222Pepperl+Fuchs Group
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
USA: +1 330 486 0002 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
pa-info@de.pepperl-fuchs.com
Technical Data
Electromagnetic compatibility
Directive 2014/30/EU Refer to DoC for all directives and standards met.
Conformity
Electromagnetic compatibility NE 21:2006
Degree of protection EN 60529
Shock resistance EN 60068-2-27
Vibration resistance EN 60068-2-6
Ambient conditions
Ambient temperature -25 ... 70 °C (-13 ... 158 °F)
Storage temperature -40 ... 85 °C (-40 ... 185 °F)
Relative humidity < 95 % , noncondensing
Shock resistance 15 g , 11 ms
Vibration resistance 1 g , 58 ... 150 Hz
Mechanical specifications
Core cross section input terminals: 4 mm
2
(10 AWG)
output terminals: 10 mm
2
(6 AWG)
Housing material Powder Coated, 1010 Cold Rolled Steel
Degree of protection IP20
Mass approx. 2.9 kg ( 6.375 lbs )
Dimensions 193 x 78 x 486 mm (7.6 x 3.1 x 19.1 inch)
Data for application in connection with hazardous areas
Certificate DEMKO 12 ATEX 1103387X
Marking 1 II 3 G Ex ec IIC T4 Gc
International approvals
UL approval cULus Listed
E230669
E350173
Approved for Class I/Div 2, ABCD
Class I, Zone 2, Grp IIC T4
IECEx approval IECEx UL 13.0082X
Ex ec IIC T4 Gc
General information
Supplementary information Statement of Conformity, Declaration of Conformity, Attestation of Conformity and
instructions have to be observed where applicable. For information see www.pepperl-
fuchs.com.
PS3500 Power Supply Backplane - 6-position PS3500-TB-6
Release date: 2022-02-08 Date of issue: 2022-02-08 Filename: 911113_eng.pdf
2
Germany: +49 621 776 2222Pepperl+Fuchs Group
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
USA: +1 330 486 0002 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
pa-info@de.pepperl-fuchs.com