ISOLATED RAIL
ISOLATED
COMMON
BOURNS
®
MODEL 2027-15-B
GAS DISCHARGE TUBE
EQUIPMENT
COMMON AND/OR
GROUND
COMMON
GROUND
BLDG. 1 BLDG. 2
COMMON
GROUND
EQUIPMENT
COMMON AND/OR
GROUND
Figure 1
BALANCED OR DIFFERENTIAL INTERFACE
(i.e., RS-422)
EQUIPMENT
COMMON AND/OR
GROUND
COMMON
GROUND
BLDG. 1 BLDG. 2
COMMON
GROUND
EQUIPMENT
COMMON AND/OR
GROUND
EQUIPMENT
COMMON AND/OR
GROUND
COMMON
GROUND
BLDG. 1 BLDG. 2
COMMON
GROUND
EQUIPMENT
COMMON AND/OR
GROUND
Figure 3
CURRENT LOOP, 4-20 mA
1800 Series
Data Line Protector
INSTALLATION INSTRUCTIONS
Specifi cations are subject to change without notice.
The device characteristics and parameters in this data sheet can and do vary in different applications and actual device performance may vary over time.
Users should verify actual device performance in their specifi c applications.
Bourns
Part No.
Peak
Signal
Voltage
Series DC
Resistance
Per Line
Max.
Short
Circuit
Current
Recommended
Fuse rating
1810 / 1820-10 10 V 10 Ω 220 mA 200 mA
1810 / 1820-15 15 V 15 Ω 180 mA 150 mA
1811 / 1820-28 28 V 22 Ω 150 mA 125 mA
1812 / 1820-50 50 V 51 Ω 75 mA 75 mA
Bourns
®
Model 1800 Series Data Line Protectors provide bi-
directional protection. Therefore, they can be used in both
positive and negative supply systems.
Each 1800 Series unit protects one differential pair (see Fig. 1),
or two individual data lines (see Fig. 2), or one current loop (see
Fig. 3). Cable shields can be passed through and may either be
grounded or not grounded at the protector via the grounding link
as shown in Fig. 4.
Place protector(s) as close as possible to the equipment to be
protected.
General
Typical Connections
WARNING: If maximum continuous or short circuit current may
exceed specifi ed values, a current-limiting fuse must
be installed between the power supply or current source and the
equipment side of the protector. See above table.
Bourns
Part No.
Peak
Signal
Voltage
Series DC
Resistance
Per Line
Max.
Short
Circuit
Current
Recommended
Fuse rating
1810 / 1821-10 10 V 10 Ω 350 mA 300 mA
1810 / 1821-15 15 V 15 Ω 300 mA 300 mA
1811 / 1821-28 28 V 22 Ω 250 mA 250 mA
IMPORTANT: Common Ground = Chassis, Power and Earth
Ground. However, when earth grounding of electronic common
is not permissible, protector(s), including rail, may have to be
isolated from earth ground via a Bourns
®
Model 2027-15-B
Spark Gap as shown in Fig. 4.
Figure 2
UNBALANCED INTERFACE - TWO INDIVIDUAL CIRCUITS
(i.e., RS-232)
Figure 4
WHEN EARTH
GROUNDING IS NOT
PERMISSIBLE
BUSBAR
PLATE
ORILL #29
TAP 8-32 INF-28
9.53
(0.375)
19.05
(0.75)
3.45
(0.136)
DIA.
ORILL #38
2.57
(0.101)
DIA.
ALIGNMENT
PIN
48.51
(1.91)
MOUNTING/
GROUNDING
SCREW
95.25
(3.75)
FEED-THRU (E3/L3)
GROUNDING
SCREW
3.18
(.125)
8-32 UNF-2A
44.45
(1.75)
LENGTH
23.62
(0.93)
DIA.
27.94
(1.1)
TS-35 RAIL MOUNTING (See Figure 5)
1. Using the clamp assembly, each protector can be installed or
removed without disturbing other protectors.
2. Protector establishes ground connections with the rail via the
clamp assembly. Tighten screw fi rmly.
3. Rail must be connected to common ground. A solid or
stranded No. 6 AWG tin-plated copper wire is recommended.
Length to be as short as possible and not to exceed 10 feet.
BUS BAR OR PLATE MOUNTING (See Figure 6)
1. Remove clamp assembly from protector.
2. Drill and tap bus bar or plate as shown.
3. Protector establishes ground connection with the bus bar or
plate via the 8-32 mounting/grounding screw. Tighten fi rmly.
4. Bus bar or plate must be connected to common ground.
A solid or stranded No. 6 AWG tin-plated copper wire is
recommended. Length to be as short as possible and not to
exceed 10 feet.
Mounting Instructions
WIRE PREPARATION
Minimum usable wire size is No. 24 AWG. Maximum usable wire
size is No. 14 AWG. Strip insulation to 0.3 inches.
LINE TERMINALS L1, L2, L3
Connect the line (fi eld) wires which are subject to high voltage
surges to protector terminals L1 and/or L2. Connect the cable
shield (if any) to protector terminal L3. L3 is internally connected
to E3.
WARNING: Never connect fi eld lines which are subject to
high voltage surges to the protector equipment terminals
E1 and/or E2. The protector may be damaged.
EQUIPMENT TERMINALS E1, E2, E3
Connect the equipment to be protected to protector terminals E1
and/or E2. Connect the cable shield (if any) to protector terminal
E3 unless it is desirable to fl oat the shield at this point (see
Figures 1 and 2). E3 is internally connected to L3.
SHIELD GROUND OPTIONS (See Figure 4)
The shield is normally grounded at the protector with the E3/L3
grounding link in position A. If the shield is to be ungrounded,
move the grounding link to position B. Re-tighten mounting and
grounding screws fi rmly.
Data Line Connections (See Figures 1-3)
Specifi cations are subject to change without notice.
The device characteristics and parameters in this data sheet can and do vary in different applications and actual device performance may vary over time.
Users should verify actual device performance in their specifi c applications.
10/13
Asia-Pacifi c: Tel: +886-2 2562-4117 • Fax: +886-2 2562-4116
Europe: Tel: +41-41 768 5555 • Fax: +41-41 768 5510
The Americas: Tel: +1-951 781-5500 • Fax: +1-951 781-5700
www.bourns.com
1800 Series
Data Line Protector
INSTALLATION INSTRUCTIONS
RAIL
E3/L3
GROUNDING
LINK
18.80
(0.74)
83.31
(3.28)
MOUNTING/GROUNDING
SCREW
FEED-THRU (E3/L3)
GROUNDING SCREW
CLAMP
ASSEMBLY
TS-32 RAIL P/N 36213
28.96
(1.14)
49.02
(1.93)
Figure 5
TS-32 RAIL MOUNTING
Figure 6
RECOMMENDED BUS BAR OR PLATE MOUNTING