1. Introduction
This application note provides step-by-step
instructions on how to connect the ZW-REC
receiver with UW series end devices. The ZW-REC
can connect up to 127 compatible wireless end
devices. Before you can connect your wireless
receiver and end device(s),
OMEGA’s TC Central measurement and data
logging program is required to configure the
UW series end devices, to then connect to the
ZW-REC. TC Central can be found at
http://www.omega.com/software/. For details on
how to properly install and use TC Central,
please refer to the UW Series manual.
http://www.omega.com/Manuals/manualpdf/
M4432.pdf
2. ZW-REC Configurations
The radio PAN ID (PID) from the ZW-REC, is
similar to the Network ID, and is required for
setting up the UW series end devices. The
PID can be found on the ZW-REC webpage
http://192.168.1.200/system.html.
• Default user name: admin
• Password: 00000000.
Connect ZW-REC with UW Series End Device
TECH NOTES
In the figure above the PID is 13110.
© 2017 OMEGA Engineering, Inc. All rights reserved.
omega.com / info@omega.com / 800.826.6342
The figure and table below show another option to obtain the PID from the DIP switches located on
the back of the ZW-REC.
Switch
NID PAN ID
8 7 6 5
OFF OFF OFF OFF 0 13106
OFF OFF OFF ON 1 13107
OFF OFF ON OFF 2 13108
OFF OFF ON ON 3 13109
OFF ON OFF OFF 4 13110
OFF ON OFF ON 5 13111
OFF ON ON OFF 6 13112
OFF ON ON ON 7 13113
Switch
NID PAN ID
8 7 6 5
ON OFF OFF OFF 8 13114
ON OFF OFF ON 9 13115
ON OFF ON OFF 10 13116
ON OFF ON ON 11 13117
ON ON OFF OFF 12 13118
ON ON OFF ON 13 13119
ON ON ON OFF 14 13120
ON ON ON ON 15 13121
Record the PID, this will be entered as the network ID for the UW end device.