HST080B
1/3
Open loop split core type,Sub-plate installationterminal output.Detect DC,AC and pulse
currentHigh insulation between primary side and the vice side circuit.
Hall split core current sensor
Back view
Fixed hole view
Front view Opening view
Installation diagram
Product features
Light weight
Low power consumption
Good linearity
No insertion loss
Fast response time
Good anti-interference ability
Product application
Railway
Metallurgical
Welding machine
Robot
Motor
Inverter power supply
Variable frequency governor
Uninterrupted power supply and communication power supply
www.poweruc.pl
1.Loosen the screw
2.Open up
3.In the lead 4.Tighten the screws
2/3
±4V
1%
1%
±12V/±15V
≤±16mA
≥10KΩ
≤±15mV
≤5μs
643g
-10~+70℃
-25~+70℃
DC~10KHz
3KV 50Hz 1min
I=I
PN
I=0~
±
I
PN
TA=25℃
±500A
±600A
±800A ±1000A
±600A ±720A
±960A ±1200A
±1200A ±1500A
±1800A
±1440A
I
PN
Ipm
Vout
X
εL
Vc
Ic
Rl
Voe
Tr
N.w
Ta
Ts
Bw
Vd
Electrical parameters:The following parameters are typical values and actual values
will be subject to product testing
Remarks:
Rated input
Input
measurement range
Rated output
Accuracy
Linearity
Supply voltage
Current consumption
Load impedance
Zero offset voltage
Response time
Weight
Operation temperature
Storage temperature
Band width
Delectric strength
Default is 1.2 times of rated input
One or the other Supply voltage range±5%
Standard output
Standard input
Reference will be subject to the measured
Reference will be subject to the measured
Reference will be subject to the measured
Factory test according to DC
Collection port impedance while lower
voltage affect accuracy
Instructions for use
1.According to the connection mode of correct connection
2.The direction shown by the arrow is positive
3.With hole measurement, response time and following the speed for the best
4.Faulty wiring can lead to product damage and output uncertainty
As our products are constantly being improved and updated, we reserve the right to modify the content
of this specification at any time without prior notice.
Safe operation:
*Please read this specification carefully before use.
*When you need to move the product, please be sure to disconnect the power and all the connected cables.
*If found shell, devices attached to the fixed parts, wire, or have any damaged, please immediately
deal with hidden dangers.
*If there is any doubt about the safe operation of the equipment, the equipment and the corresponding
accessories should be closed immediately, and the fastest time for troubleshooting.
Proclamations
www.poweruc.pl