THST080D
1/3
Hall split core current transducer
Sub-plate mount terminal output.Detect DC current. High insulation between primary and secondary
circuits.
1.Loosen the screw
2.Open up
3.In the lead 4.Tighten the screws
Installation diagram
Product features
Light weight
Low power consumption
Good linearity
No insertion loss
Fast response time
Good anti-interference ability
Product application
Railway
Metallurgical
Welding machine
Robot
Motor
Inverter power supply
Variable frequency governor
Uninterrupted power supply and communication power supply
www.poweruc.pl
2/3
400A
480A
500A 600A
720A600A
800A 1000A 1500A
1800A
2000A
2400A1200A960A
TA=25℃
0-20mA/4-20mA/0-5V/1-5V/0-10V
1%
0.5%
+12V / +24V
48mA+Io
350mS
648g
-10+70
-25+70
DC400Hz
3KV 50Hz 1min
Remarks
Electrical parameters:The following parameters are typical values and actual values
will be subject to product testing
Rated input
Input
measurement range
Rated output
Accuracy
Linearity
Supply voltage(±5%)
Current consumption
Load impedance
Zero offset voltage
Response time
weight
Operating temperature
Storage temperature
Band width
Delectric strength
Voltage type output
≥10KΩ
Current type output
250Ω(Typification
)
Current type output
±0.08mA
Voltage type output
±15mV
Output one of five
0-10V output +24V power supply
Standard input
Default is 1.2 times the input rating
Reference will be subject to the measured
Reference will be subject to the measured
Reference will be subject to the measured
Instruction for use
1.Connect the wires correctly according to the marked connection mode
2.The direction indicated by an arrow for the positive current direction
3.With hole measurement, response time and following the speed for the best
4.Faulty wiring can lead to product damage and output uncertainty
As our products are constantly being improved and updated, we reserve the right to modify the content
of this specification at any time without prior notice.
Safe operation:
*Please read this specification carefully before use.
*When you need to move the product, please be sure to disconnect the power and all the connected cables.
*If found shell, devices attached to the fixed parts, wire, or have any damaged, please immediately
deal with hidden dangers.
*If there is any doubt about the safe operation of the equipment, the equipment and the corresponding
accessories should be closed immediately, and the fastest time for troubleshooting.
Proclamations
www.poweruc.pl
One or the other Supply voltage range ±5%