3-349-819-03
3/6.18
GMC-I Messtechnik GmbH
METRISO PRIME
High-Voltage Insulation Tester
for battery or hand crank generator operation
Features
Test Voltages to 5000 V
This instrument is suited for the non-destructive measurement of
insulation resistance in electrical systems, at machines and trans-
formers and in cables, as well as within the electrical equipment
of, for example, locomotives, tram systems and ocean going ves-
sels, with eight selectable test voltages up to 5 kV.
Voltage Measurement to 2000 V
With the voltage measuring ranges, test objects can be checked
for the absence of voltage in networks of up to 2 kV. This is
important for insulation resistance measurement, because extra-
neous voltages distort measurement results.
Discharge of Capacitive Devices Under Test
Capacitive devices under test such as cables and coils, which
might be discharged to test voltage, are discharged by the mea-
suring instrument. The drop in voltage can be observed at the
needle gauge.
Measurements in accordance with EN 61557 part 1 and 2 (VDE 0413)
Measuring current is equal to 1 mA at a test voltage of 100 V,
250 V, 500 V and 1000 V.
Measurement Cables with Heavy-Duty Insulation
The measurement cables with heavy-duty insulation are perma-
nently connected for safety and technical reasons. Possible dan-
ger caused by the unintentional removal of cables is thus avoided,
for example when charging occurs due to capacitive test objects.
Needle Gauge with LEDs
Three LEDs arranged within the needle gauge make reading eas-
ier. The lamp lights up which is located next to the scale, which is
assigned to the selected measuring range. During the measure-
ment sequence, the green LED indicates whether or not the bat-
tery charge is sufficient for the measurement.
Applicable Regulations and Standards
IEC 61010-1:2010
DIN EN 61010-1:2011
VDE 0411-1:2011
Safety regulations for electrical measurement,
control, regulation and lab devices
– General requirements
IEC 61010-031: 2015
DIN EN 61010-031: 2016
VDE 0411-031:2016
Safety requirements for electrical equipment for measure-
ment, control and laboratory use.
Part 031. Safety requirements for hand-held probe assemblies
for electrical measurement and test
IEC 61010-2-030:2010
DIN EN 61010-2-
030:2011
VDE 0411-2-030:2011
Safety requirements for electrical equipment for measure-
ment, control and laboratory use.
Part 2-030: Particular requirements for testing and measuring
circuits
IEC 61557
DIN EN 61557
-1:2007
-2:2008
VDE 0413
-1:2007
-2:2008
Measuring and monitoring facilities
for testing the electrical safety in lines
with nominal voltages up to AC 1000 V and DC 1500 V
Part 1 General
Part 2 – Insulation resistance measuring devices
IEC 61326-1:2012
DIN EN 61326-1:2013
VDE 0843-20-1:2013
Generic Emission Standard; Electrical equipment for
measurement, control and laboratory use
– EMC requirements
Part 1 – General requirements
DIN EN 60529:2014
VDE 0470-1:2014
Test instruments and test procedures
– degree of protection provided by enclosures (IP code)
Broad measuring range from 10 kΩ to 1 TΩ
Easy to read logarithmic display
Test voltages:
100 V, 250 V, 500 V, 1000 V, 1500 V, 2000 V, 2500 V, 5000 V
Measurement to 2000 V in accordance with DIN VDE 0413
Measuring range: 100 kΩ to 100 MΩ (1000 V)
Voltage measurement to 2000 V ,
Guard terminal eliminates surface current
5 m extension cable as accessory equipment
Power supply with batteries or hand crank generator (optional)
Applications
Insulation measurement for cables, motors etc.
METRISO PRIME
High-Voltage Insulation Tester
for battery or hand crank generator operation
2 GMC-I Messtechnik GmbH
Measuring Ranges
Insulation Resistance
ShortCircuit Current I
K
1.3 mA
Making Capacity for Insulation Resistance Measurement
Response Time < 100 GΩ: <3s; >100GΩ: <8s
also valid for test voltage or measuring
range changes
Direct and Alternating Voltage
Protective Devices
1)
with reference to scale length 97.5 mm (100 MΩ range) or 109.8 mm (1 TΩ range)
2)
PTC resistor cool-down period until start of new measurement:
at least 2 minutes must be observed!
Display
Movement Core-magnet moving-coil mechanism
Scale length 111.5 mm (longest scale)
Reference Conditions
Ambient
Temperature + 23 °C ±2K
Relative Humidity 40 ... 60%
Meas. Quantity
Frequency 50 Hz ±10 Hz
(for voltage measurements)
Line Voltage
Waveform Sine, deviation between effective
and rectified value < 1%
Battery voltage 8 V ± 1%
Operating position Horizontal
Power Supply
Standard or
Storage Battery 6 ea. 1.5 V single cell per IEC R20
(6 x D-Size)
Working Range 6 V ... 10 V
Battery Service Life 7500 measurements for test voltage of
1000 V with meas. resistance of 1 MΩ,
15000 measurements for test voltage
of 500 V with meas. resist. of 500 kΩ,
measurement of 5 s – pause 25 s
Crank Generator (optional) 2 to 3 r.p.s. with moderate strength,
the LED Ω signals sufficient crank
frequency and consequently the vali-
dity of measuring values
Nominal Voltage 7.5 V (at approx. 2.5 r.p.s.)
Nominal Power 4 W (at approx. 2.5 r.p.s.)
Ambient Conditions
Operating Temperature 0 °C ... + 40 °C
Storage Temperature 20 °C ... + 60 °C (without batteries)
Relative Humidity max. 75%,
condensation must be avoided
Elevation up to 2000 m
Scale/
Stan-
dard
Mea-
suring
Range
Nominal
Range of
Use
Nominal/Test
Voltage
U
N
/ U
T
Nom./Test
Current
I
N
/ I
T
Intrinsic
Uncer-
tainty
1)
Measuring
Uncer-
tainty
VDE0413
100 kΩ
...
100 MΩ
100 kΩ
... 10 MΩ
100 V
250 V
500 V
1000 V
1mA
± 2.5%
±30%
of measu-
red value
10 kΩ
... 1 TΩ
100 kΩ
...
100 GΩ
100/1500 V
250/
2000 V
500/
2500 V
1000/5000 V
1 mA/0.7 mA
1 mA/0.5 mA
1 mA/0.4 mA
1 mA/0.1 mA
± 5%
Measuring range Frequency Internal
resistance
Max. allowable
voltage
Intrinsic error
1)
0 ... 2000 V AC/DC 15 ... 500 Hz 5 MΩ 2200 V AC/DC
max. 10 s
± 5%
Terminal Internal
Resistance
Max. Allowable
Voltage
Protective Device
–Measurement
cable
��
to +meas. cable/
to Guard cable:
2000 V DC/AC
max. 10 s
via grounded damping
diodes
+Measurement
cable
Insulation
measurement
to –meas. cable/
to Guard cable:
2000 V DC/AC
max. 10 s
Diodes in high-voltage
cascade,
PTC thermistor
2)
and
series resistors
Guard cable
between Guard
and meas. cables
90 kΩ
to meas. cable
2000 V DC/AC
max. 10 s
PTC thermistor
2)
and
series resistors
Battery 10 V
Pole protection with diodes
voltage limiting in battery
charger (optional)
1
2
1
2