GMC-I Messtechnik GmbH
METRISO 5000 A/AK
High-Voltage Insulation Tester
Features
Test Voltages to 5000 V
This instrument is suited for the non-destructive measurement of
insulation resistance in electrical systems, at machines and trans-
formers and in cables, as well as within the electrical equipment
of, for example, locomotives, tram systems and ocean going ves-
sels, with eight selectable test voltages up to 5 kV.
Voltage Measurement to 2000 V
With the voltage measuring ranges, test objects can be checked
for the absence of voltage in networks of up to 2 kV. This is
important for insulation resistance measurement, because extra-
neous voltages distort measurement results.
Discharge of Capacitive Devices Under Test
Capacitive devices under test such as cables and coils, which
might be discharged to test voltage, are discharged by the mea-
suring instrument. The drop in voltage can be observed at the
needle gauge.
Measurements in accordance with EN 61557 part 1 and 2 (VDE 0413)
Measuring current is equal to 1 mA at a test voltage of 100 V,
250 V, 500 V and 1000 V.
Measurement Cables with Heavy-Duty Insulation
The measurement cables with heavy-duty insulation are perma-
nently connected for safety and technical reasons. Possible dan-
ger caused by the unintentional removal of cables is thus avoided,
for example when charging occurs due to capacitive test objects.
Needle Gauge with LEDs
Three LEDs arranged within the needle gauge make reading eas-
ier. The lamp lights up which is located next to the scale, which is
assigned to the selected measuring range. During the measure-
ment sequence, the green LED indicates whether or not the bat-
tery charge is sufficient for the measurement.
Applicable Regulations and Standards
IEC 61010-1:2001
DIN EN 61010-1:2002
VDE 0411-1:2002
Safety regulations for electrical measurement,
control, regulation and lab devices
– General requirements
IEC 61557
DIN EN 61557
Part 1:2007
Part 2:2007
VDE 0413
Part 1:2007
Part 2:2008
Measuring and monitoring facilities
for testing the electrical safety in lines
with nominal voltages up to AC 1000 V and DC 1500 V
Part 1 – General
Part 2 – Insulation resistance measuring devices
IEC 61326-1:2005
DIN EN 61326-1:2006
VDE 0843-20-1:2006
Generic Emission Standard; Electrical equipment for
measurement, control and laboratory use
– EMC requirements
Part 1 – General requirements
DIN EN 60529
VDE 0470-1:2000
Test instruments and test procedures
– degree of protection provided by enclosures (IP code)
Broad measuring range from 10 kto 1 T
Easy to read logarithmic display
Test voltages:
100 V, 250 V, 500 V, 1000 V, 1500 V, 2000 V, 2500 V, 5000 V
Measurement to 2000 V in accordance with DIN VDE 0413
Measuring range: 100 kto 100 M (1000 V)
Voltage measurement to 2000 V ,
Guard terminal eliminates surface current
5 m extension cable as accessory equipment
Power supply with batteries or hand crank generator (optional)
Applications
Insulation measurement for cables, motors etc.
METRISO 5000 A/AK
High-Voltage Insulation Tester
2 GMC-I Messtechnik GmbH
Measuring Ranges
Insulation Resistance
Making Capacity for Insulation Resistance Measurement
Response Time < 100 G <3s; >100G <8s
also valid for test voltage or measuring
range changes
Direct and Alternating Voltage
Protective Devices
1)
with reference to scale length 97.5 mm (100 M range) or 109.8 mm (1 Trange)
2)
PTC resistor cool-down period until start of new measurement:
at least 2 minutes must be observed!
Display
Movement Core-magnet moving-coil mechanism
Scale length 111.5 mm (longest scale)
Reference Conditions
Ambient
Temperature + 23 C 2K
Relative Humidity 40 ... 60%
Meas. Quantity
Frequency 50 Hz 10 Hz
(for voltage measurements)
Line Voltage
Waveform Sine, deviation between effective
and rectified value < 1%
Battery voltage 8 V1%
Operating position Horizontal
Power Supply
Standard or
Storage Battery 6 ea. 1.5 V single cell per IEC R20
(6 x D-Size)
Working Range 6 V ... 10 V
Battery Service Life 7500 measurements for test voltage of
1000 V with meas. resistance of 1 M,
15000 measurements for test voltage
of 500 V with meas. resist. of 500 k,
measurement of 5 s – pause 25 s
Crank Generator (optional) 2 to 3 r.p.s. with moderate strength,
the LED signals sufficient crank
frequency and consequently the vali-
dity of measuring values
Nominal Voltage 7.5 V (at approx. 2.5 r.p.s.)
Nominal Power 4 W (at approx. 2.5 r.p.s.)
Ambient Conditions
Operating Temperature 0 C ... + 40 C
Storage Temperature 20 C ... + 60 C (without batteries)
Relative Humidity max. 75%,
condensation must be avoided
Elevation up to 2000 m
Scale/
Stan-
dard
Measu-
ring
Range
Nominal
Range of
Use
Nominal/
Open-
Circuit
Voltage
U
N
/U
0
Nom.
Current
I
N
Short-
Circuit
Current
I
K
Intrin-
sic
Error
1)
Deviation
VDE0413
100 k
...
100 M
100 k
... 10 M
100 V
250 V
500 V
1000 V
1mA 1.3mA
2.5%
30%
of measu-
red value
10 k
... 1 T
100 k
...
100 G
100/1500 V
250/
2000 V
500/
2500 V
1000/
5000 V
0.7 mA
0.5 mA
0.4 mA
0.1 mA
1.3 mA
5%
Measuring range Frequency Internal
resistance
Max. allowable
voltage
Intrinsic error
1)
0 ... 2000 V AC/DC 15 ... 500 Hz 5 M 2200 V AC/DC
max. 10 s
5%
Terminal Internal
Resistance
Max. Allowable
Voltage
Protective Device
–Measurement
cable
to +meas. cable/
to Guard cable:
2000 V DC/AC
max. 10 s
via grounded damping
diodes
+Measurement
cable
Insulation
measurement
to –meas. cable/
to Guard cable:
2000 V DC/AC
max. 10 s
Diodes in high-voltage
cascade,
PTC thermistor
2)
and
series resistors
Guard cable
between Guard
and meas. cables
90 k
to meas. cable
2000 V DC/AC
max. 10 s
PTC thermistor
2)
and
series resistors
Battery 10 V
Pole protection with diodes
voltage limiting in battery
charger (optional)
1
2
1
2