Raychem-DS-H58621-ProtoNode-EN-1812 nVent.com
|
1
PROTONODE
MULTI-PROTOCOL DEVICE GATEWAY
PROTONODE-RER AND PROTONODE-RER-10K
PRODUCT OVERVIEW
The nVent RAYCHEM ProtoNode is an external, high
performance multi-protocol gateway for customers needing
protocol translation between Building Management Systems
(BMS) using BACnet® or Metasys® N2 and the RAYCHEM
C910-485, ACS-30 or TTSIM controllers.
The RAYCHEM ProtoNode-RER and ProtoNode-RER-10K
come pre-programmed with the C910-485, ACS-30 and TTSIM
Modbus® profiles for simple integration into a BMS. One
ProtoNode can connect to: one ACS-30 system or up to six
C910-485 controllers or up to one hundred TTSIM modules.
ProtoNode-RER: Provides support for Modbus RTU to
BACnet MS/TP, BACnet IP (BTLCertified), and Metasys N2
protocol translation for C910-485, TTSIM and smaller scale
ACS-30 systems (up to 5 PCM panels). The gateway features
an ARM9 processor for fast performance and includes two
RS-485 and one Ethernet ports.
ProtoNode-RER-10K: Provides support for Modbus RTU
to BACnet MS/TP, BACnet IP (BTLCertified), and Metasys
N2 protocol translation for larger ACS-30 systems (up to 34
PCM panels). The gateway features an ARM9 processor
for fast performance and includes two RS-485 and one
Ethernet ports.
Features and benets:
The most flexible and versatile multiprotocol device
server on the market
BACnet International’s BTL Certification makes the
ProtoNode-RER the most reliable gateway on the
market
Multi-client and multi-server support ensures
interoperability between any Industrial and or
Building Automation protocols
Flash upgradable
For additional information, contact your nVent representative
or call (800) 545-6258.
APPROVALS
BACnet Testing Labs (BTL) B-ASC on ProtoNode-RER
GUI
BMS
Modbus TCP
BACnet IP
Ethernet (TCP/IP)
BACnet MS/TP
Metasys N2 by JCI
Ethernet to
Serial
ProtoNode-RER
By FieldServer Technologies
www.ProtoCessor.com
PROTOCESSOR
SERIAL ETHERNET
PROTONODE
FRAME GND
- PWR
+PWR
RS 485+
RS 485 -
RS 485 GND
S3
S2
S1
S0
B3
B2
B1
B0
A7
A6
A5
A4
A3
A2
A1
A0
To C910-485 ,
TTSIM and ACS-30
controllers
©2018 nVent. All nVent marks and logos are owned or licensed by nVent Services GmbH or its affiliates. All other trademarks are the property of their respective owners.
nVent reserves the right to change specifications without notice.
Our powerful portfolio of brands:
CADDY ERICO HOFFMAN RAYCHEM SCHROFF TRACERnVent.com
Raychem-DS-H58621-ProtoNode-EN-1812
North America
Tel +1.800.545.6258
Fax +1.800.527.5703
info@nvent.com
2
SPECIFICATIONS
ProtoNode-RER & ProtoNode-RER-10K
Electrical connections One 6-pin Phoenix connector, one RS-485 +/- ground port, power +/- frame
ground port
One 3-pin RS-485 Phoenix connector, one RS-485 +/- ground port
One Ethernet-10/100 Ethernet port
Power requirements 930 Vdc or Vac, or 5 Vdc
Current draw 150 mA @ 12 V
Supported field protocols BACnet IP (Ethernet)
BACnet MS/TP (RS-485)
Metasys N2 open (RS-485)
Operating temperature 40°F to 187°F (–40°C to 85°C)
Relative humidity 590% RH, noncondensing
Enclosure dimensions 4.37 in L x 2.75 in W x 1.50 in H
(11.10 cm L x 7.00 cm W x 3.81 cm H)
NUMBER OF PROTONODE / CONTROLLER CONNECTIONS
Description ProtoNode-RER ProtoNode-RER-10K
C910-485 6 N/A
TTSIM modules 100 N/A
ACS-PCM2-5 Panels 5 34
ORDERING DETAILS
Description Catalog number Part number Weight (lbs)
RAYCHEM ProtoNode-RER:
BACnet MSTP/IP and Metasys N2
protocolgateway
ProtoNode-RER P000002008 1.3
RAYCHEM ProtoNode-RER-10K :
BACnet MSTP/IP and Metasys N2
protocol gateway
ProtoNode-RER-10K P000001983 1.3