EPC Circuit Breakers and
Enclosures with Interlocked
Arktite
®
Receptacles
APJ/NPJ† and DP Arktite Plugs
Cl. I, Div. 1 and 2, Groups C, D
Cl. II, Div. 1 and 2, Groups F, G
Cl. III
NEMA/EFC 3, 7CD, 9FG, 12
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
Applications:
• The EPC interlock receptacle is
designed for use as a service outlet for
portable equipment
• It is designed for use in damp, wet and
corrosive locations, indoors or outdoors,
in areas which are hazardous due to
flammable vapors, gases or combustible
dust. For example: refineries, chemical
plants, and other processing and
handling facilities of a hazardous nature
Features:
• Mechanical interlock mechanism for
dead front construction
• Receptacles are mechanically
interlocked with circuit breakers to
provide disconnect means, short circuit
protection and thermal time delay
overload protection
• A spring door receptacle, located at
bottom of 30, 60 and 100 ampere units
and at front of 200 ampere units, is
mechanically interlocked with the circuit
breaker operating mechanism for
maximum safety
• Plug and receptacle contacts cannot be
made or broken under load. The circuit
breaker cannot be closed until the plug
is fully inserted and the plug cannot be
withdrawn unless the breaker is open
• Operating handles can be padlocked in
either "ON" or "OFF" positions. Breakers
are trip-free of the handles and will open
under short circuit or overload even if
the handle is locked in the "ON" position
• Quick installation and leveling is
provided by the three-point mounting
arrangement which has one keyhole slot
at top and two open slots at bottom
• Bodies have four taper-tapped conduit
hubs with integral bushings. Two are
located at top and two directly below.
Sizes are as shown in the listings.
Grounding:
• EPC interlocked receptacles and
matching plugs are provided with an
extra grounding pole for attaching a
grounding wire. In addition, direct
connection is provided between plug
and receptacle and the grounding pole.
If a separate grounding wire is not
installed in the enclosure, grounding is
accomplished through the conduit
system.
Standard Materials:
• Bodies, covers and receptacle housings
– copper-free aluminum
• Operating handles – copper-free
aluminum
• Operating shafts – stainless steel
• Interior parts – sheet steel
• Insulation (receptacles and plugs) –
fiberglass-reinforced polyester
• Pressure contacts – brass
• Crimp/solder contacts – leaded red
brass
Standard Finishes:
• Copper-free aluminum – natural
• Stainless steel – natural
• Sheet steel – electrogalvanized with
chromate finish
• Brass – natural
• Fiberglass-reinforced polyester – natural
(red)
• Leaded red brass – electro-tin-plate
Electrical Rating Ranges:
• Receptacle ratings: 30, 60, 100 and 200
amperes
• Circuit breakers: 100 and 225 ampere
frame sizes
Certifications and
Compliances:
• NEC:
Class I, Division 1 and 2, Groups C, D
Class II, Division 1 and 2, Groups F, G
Class III
• NEMA: 3, 7CD, 9FG, 12
• ANSI/UL Standard: 1010
• CEC:
Class I, Division 1 and 2, Groups C, D
Class II, Division 1 and 2, Group G
Class III
Encl. 3, 4
30, 60 and 100 ampere size EPC
200 ampere size EPC
Options:
The following special options are available by adding suffix to Cat. #:
Description Suffix
Special polarity – used where two or more receptacles of the same ampere rating,
style and number of poles are to be installed in the same area for use on different
voltages. Available on 30, 60 and 100 ampere units as follows:
Receptacle interior rotated 22
1
/2° clockwise when viewed from face of receptacle
and plug changed to match...........................................................................................
S4
Side bosses drilled and tapped same size as standard hubs, 30, 60 and
100 ampere units only ...................................................................................................
S366
Back boss drilled and tapped same size as standard hubs, 30, 60 and
100 ampere units only ...................................................................................................
S367
Breather and drain (Class I, Class II) .............................................................................
S198V
Breather and drain (Class I only)....................................................................................
S454V
CAUTION: To reduce the risk of ignition of hazardous atmospheres, do not use plugs or receptacles in Class II, Group F
locations that contain electrically conductive dusts.
†Pressure connectors are standard. Crimp/solder type terminators are optionally available for 2, 3 and 4-pole 30 ampere,
3 and 4-pole 60 and 100 ampere. For details, see page 1316. To specify, add the suffix "T" to the catalog number.
For example: APJ3365-T (Plug).