42
Functions PN9108U PN0108
Power Inlet 1x IEC 60320/C14 Male
Power Outlets 8 x IEC 60320/C13 Female
Connectors PON In 1 x DB-9 Female (Black)
PON Out 1 x DB-9 Male (Black)
Safe Shutdown 8 x 6-pin safe shutdown jacks Female
LAN 1 x RJ-45 Female -
Switches Reset 1 x Semi-recessed Pushbutton
Power 1 x Rocker
Station ID Display 1 x Pushbutton -
Outlet On/Off 8 x Pushbutton
Remote On/Off
LED Outlet Power 8 (Orange)
Remote Access 8 (Green)
Link 1 (Green) -
10/100 Mpbs 1 (Orange/Green) -
Power 1 (Blue) -
Current 1 (Red) -
Station ID Display 2 x 7 Segment (Orange)
Iutput Rating 100-120V; 50/60Hz, 12A
Output Rating Per Port 100-120V; 50/60Hz, 9A(Max)
Total 100-120V; 50/60Hz, 11A(Max)
Power Consumption No Load 120V/16W
Max Load 120V/1440W
Environment Operating Temp. 32˚~122˚F (0˚~ 50˚C)
Storage Temp. -4˚~140˚F (-20˚~ 60˚C)
Humidity 0~80% RH, Non-condensing
Physical Properties Housing Metal
Weight 9.2 lb. (4.2 Kg) 8.1 lb. (3.7 Kg)
Dimension (LxWxH) 17.2x10.0x1.7 in. (43.7 x 25.4 x 4.4 cm)
PN0108
PN0108
Internet/LAN
CN-5000/PN9108U
KN9116/KN9108
KN2108/KN2116
SN0108/SN0116
*Up to additional PN0108 can be daisy chained
IP Ready
TCP/IP
Removable front panel for ease of access and cable management
Daisy chaining option to support up to 128 attached computers
Network remote power on/off/reboot control via TCP/IP 10/100
Ethernet port. (PN0108 does not come with IP capability, it can only
be used with other IP devices. See diagram.)
Local power on/off control via RS-232 port to local device. Manual
switching between the local control and remote control via front panel
interface
Easy setup and operation through 3 interfaces - Browser, Telnet, or
Console Terminal
Safe shutdown and rebooting for application management and limiting
downtime
Sequenced and delayed power settings for port prioritization and
circuit overload prevention
Cumulative load measurement - allows remote/local users to measure
and manage power diagnostics
Over current protection- to prevent damaging input voltages from
reaching attached sensitive equipment
On/Off scheduling function - allows administrators the ability to create
general or specifi c shutdown/restart schedules to facilitate system
management
Port grouping function - allows administrators the ability to group ports
and expedite operations
Firmware upgradeable over Internet via the RJ45 LAN Port or remote
IP connection
Package Contents
1 x PN9108U or PN0108
1 x AC power cord
8 x power outlet power cord
8 x safe shutdown cable
1 x rack mount kit
Diagram
Specifi cations
8-port Power Over the NET™
PN9108U
PN0108
Advantages
Diagram
IP Upgradeable
TCP/IP
POWER CONTROL SOLUTIONS