Ver.1.03
CPS-PWD-15AW12-01 1
CONPROSYS Series
12VDC AC-DC Power Supply Unit
CPS-PWD-15AW12-01
* Specifications, color and design of the products are subject to change without notice.
This product is an optional Power supply unit for the CPS-MC341 series
in the CONPROSYS series.* The IEEE802.3af and IEEE802.3at standards
are not supported.
Specification
Requirement
Description
Power supply space
Rated input voltage *
100 to 240VAC, 50 to 60Hz
Permissible input voltage *
85 to 264VAC, 50 to 60Hz
Input current
0.4A typ (100VAC), 0.25A typ (230VAC)
Rated output voltage
12.0VDC
Rated output current
1.3A (Max.)
Isolation
Input-Output
3000VAC 1minute 50M (500VDC)
(At room temperature)
Input-FG
2000VAC 1minute 50M (500VDC)
(At room temperature)
Output-FG
500VAC 1minute 50M (500VDC)
(At room temperature)
Environmental specs
Temperature *
Operating : -20 to +70°C,
non operating : - 20 to + 75°C
Humidity
Operating : 20 to 90%RH (No condensation)
Non operating : 20 to 90%RH (No condensation)
Floating dust particles
Not to be excessive
Corrosive gases
None
Vibration resistance
10 to 55Hz / 2.0G
Construction
Length of DC cable (mm)
200 (not include connector)
External dimensions (mm)
39.0(W)x80.0(D)x79.0(H) (not include projection)
Weight
Main body : 305g Max.
Longevity
5years
(temperature 40 C,Input 100VAC, Output 1.17A)
Standard
FCC Class B, UL/c-UL, TUV
CE Marking (EMC Directive Class B, LVD, RoHS Directive)
* The derating is required.
Packing List
Power Supply …1
Product gu ide … 1
Serial Number Label …1
DC Ca bl e …1
Warr anty Certificate …1
List of Option
AC power cable
IPC-ACCODE3 : AC cable with 3-round-end terminal
(Length : 2 m eters, Rating : 7A 125V)
* Visit the Contec website regarding information on the optional products
Physical Dimensions
80
27.2
7Max.
79
12.5Max.
2-M3
Mounting hole
39
3.5
11.29(LED)
11.6(Potentiometer)
14
VADJ
6.5
12.7
17
6.2
9.5
8.2
[mm]
(230)
(200)
6.6(Max.)
3.7(Min)
Terminal
Ver.1.03
CPS-PWD-15AW12-01 2
External Dimensions
Derating by input voltage
Figure1. below shows derating curve by input voltage.
Figure 1 Input voltage derating cu rve
Derating by operating ambient temperature
Figure 1. and Figure 2. show the derating characteristics by operating
ambient temperature. A ripple and a ripple noise specification varies in
the shadow area. This unit requires checking at temperature
measurement points as well.
(1) Temperature measurement points
Make sure the temperatures at point A and point B stay lower than the
one listed in Table a.
Confirm even under the condition of forced air, it satisfies the
temperature condition indicated in Ta ble a.
The expected lifetime of point A and point B at maximum temperature is
approximately three years. If you plan to extend the expected lifetime,
see “Expected Lifetime” (Table b.) and “Warranty” (Table c.).
Table a. Temperature of Po int A PLA15F
(2) Derating by operating ambient temperature
Figure 2 Ambient temperature derating curve for PLA15F
Operating ambient temperature indicates the place 5- 10 cm apart from
the unit side that is unaffected by the heat dissipation. Contact us for
details regarding Operating ambient temperature
Table b. Expected lifet ime
Table c. Warranty
When mounting the power unit, do not fail to connect an input FG
terminal and the unit frame (at least two places) to the ground wire.