Ver.1.02
CPS-MM-LC 1
CONPROSYS Series
Measurement Module
CPS-MM-LC
* Specifications, color and design of the products are subject to change
without notice.
This product is a module to monitor isolation resistance of the
equipment in a live state that is driven by three-phase alternating current
power. Set this module to operate along with the CONPROSYS series
configurable type CPU module controller.
It has a function useful for early deterioration discovery in the equipment
powered by the three-phase and AC motors connected to the servo
amplifier or invertors, which are widely used in the FA factories or water
treatment facilities, for instance in a pump, and the system can be
examined while power is active.
* The contents in this document are subject to change without notice.
* Visit the CONTEC website to check the latest details in the document.
* The information in the data sheets is as of November, 2019.
Hardware Features
Find isolation deterioration in AC motor
This product finds isolation deterioration of the three-phase induction
motor by calculating isolation resistance from the measured applied
voltage as well as ground fault current to the three-phase induction
motor (low pressure three-phase motor) and AC servo motor.
With the Modes-IOTM measurement method, isolation resistance in a
live state can be accurately measured, and it is applicable to detect
isolation deterioration of the three-phase induction motor of AC motor.
The product can be set either in front of or behind the inverter and the
servo amplifier.
* The measurement method of TANASHIN DENKI CO.,LTD. is applied for
this product.
Compact Design
Compact design, 25.2(W)×94.7(D)×124.8 (H), features flexibility in
installation.
Adaptable to a temperature range between -20 and +60°C
The product is capable of operating in the temperature between -20 and
+ 60°C. It can be installed in the various environments.
Installation easy with two pieces of terminal support and DIN rail
You can install and remove a terminal connector without a screwdriver so
that it can shorten the time of the replacement.
As the product can be mounted and slid on a DIN rail, removing and
replacing are easy as well.
Equipped with LED for an operation check
The product has LED for an operation check, which helps you visually
confirm the communication status of each interface.
Packing List
Product [CPS-MM-LC]…1
Product Guide…1
Warranty Certificate…1
Serial Number Label…1
4-pin Connector (Power/Analog) …3
ZCT Unit …1
Specifications
Function Specifications <Product>
Item
CPS-MM-LC
Measurement function
Leakage current measurement,
Isolation resistance measurement
Measurement method *1
Modes-IO®
The number of measurement channels
1
Applied motor type*2
Three-phase induction motor (low pressure three-phase motor),
AC servo motor
Measurement
target circuit
Motor isolation resistance
measurement
Three-phase output part (motor) of inverter /servo amplifier
powered by three-phase Delta (3-wire, three-phase corner-
grounded system), three-phase Wye (3-wire/4-wire, three-
phase solidly-grounded neutral system).
All equipment isolation
resistance
Three-phase Delta (3-wire, three-phase corner-grounded
system)
Three-phase Wye (3-wire/4-wire, three-phase solidly-grounded
neutral system)
Rated input voltage *3
Line voltage, 10VAC - 600VAC 50Hz/60Hz three-phase
Line average voltage range
0.000 VAC - 999.999 VAC
(Measurement voltage range is 10VAC-600VAC (Line voltage))
Measurement
Leakage current
range
Motor isolation resistance
measurement
0.000mA - 99.999mA
All equipment isolation
resistance
0.000mA - 999.999mA
Isolation resistance output range
0.000MΩ - 999.999MΩ
Measurement time
30sec.
Voltage value
accuracy *4 *5
Line average voltage value,
Va
±(1% of reading + 300digits)
Leakage current
value accuracy
*4 *5
(25°C±2°C)
Leakage current value, Io
±(1% of reading + 10 digits)
Leakage current value by
isolation resistance, Ior
±(1% of reading + 10 digits + Io × 0.005)
Isolation
resistance value
accuracy *4 *5*6
(25°C±2°C)
Combined isolation
resistance value, R
±(10% of reading + 100 digits) *when Io=Ior
Isolation specification
Bus Isolation
Voltage resistance *7
2200VAC
Voltage measurement connector
2-piece 7.62mm pitch 4-pin terminal
Applicable wire
AWG24 - 12
LED
Status (Green, Red)
Power voltage
24VDC ±10%
Power consumption
0.1A (Max.)
Physical dimensions (mm)
25.2(W)×94.7(D)×124.8(H) (No projection included)
Weight
200g
Installation method
Quick mounting on the 35mm DIN rail
Installation environment
Applicable pollution degree 2
*1 The patent theory of TANASHIN DENKI CO.,LTD. is applied.
*2 Inverter and servo amplifier of mono-phase power type are not applicable for measurement.
*3 Use in the circuit not exceed CAT III 300V or CAT II 600 V.
*4 The accuracy excludes the noise effects from external magnetic fields or residual magnetism.
*5 Value is when adjusted with standard jig
*6 Accuracy cannot be guaranteed for Isolation resistance value of 10MΩ or greater.
*7 Between voltage measurement connector and stack bus
CAUTION
You can set the modules as you desire to the configurable controller up to 16 modules.
The total current consumption of the modules should be less than 3.3A.
Ver.1.02
CPS-MM-LC 2
Function Specifications < ZCT unit >
Item
Structure
Rated voltage
Penetrating hole diameter
Isolation resistance
Cable length
Connector
Physical dimensions (mm)
Weight
Installation method
*8 Use an isolated cable to connect through the ZCT unit.
Function Specifications < ZCT unit >
Item
CPS-MM-LC
Operating ambient temperature
-20 - +60°C
Operating ambient humidity
10 - 90%RH (No condensation)
Non-operating ambient
temperature
-20 - +60°C
Non-operating ambient humidity
10 - 90%RH (No condensation)
Floating dust particles
Not to be excessive
Corrosive gases
None
Line-noise
resistance
Line noise
Signal Line /±1kV (IEC61000-4-4 Level 3, EN61000-4-4 Level 3)
Static electricity
resistance
Touch /±4kV (IEC61000-4-2 Level 2, EN61000-4-2 Level 2)
Air /±8kV (IEC61000-4-2 Level 3, EN61000-4-2 Level 3)
Vibration
resistance (The
product alone)
*9
Sweep
resistance
10 - 57Hz *10 /semi-amplitude vibration 0.15mm, 57 - 150Hz/2.0G
40minutes each in X, Y, and Z directions (JIS C60068-2-6-compliant,
IEC60068-2-6-compliant)
Shock resistance (The product
alone) *10
15G half-sine shock for 11ms in X, Y, and Z directions
(JIS C 60068-2-27 compliant, IEC 60068-2-27 -compliant)
Altitude
2000m or less
Pollution degree
2
Measurement category
CAT III 300V / CAT II 600V
*9 When you use an optional power product: 10 - 55Hz (See the manual of optional power product for details)
*10 Do not use the ZCT UNIT in a place subject to vibration or shock. It may lead to malfunction or shorter life of
the product.
Physical Dimensions
Product
ZCT unit
List of Option
Configurable Type Controller
CPS-MCS341-DS1-111: Configurable type CPU module
CPS-MCS341-DS1-131: Configurable type CPU module +
OPC UA server + MT Connect
CPS-MCS341G-DS1-130: Configurable type CPU module +3GWAN
CPS-MCS341Q-DS1-131: Configurable type CPU module +920MHz LAN
DIN rail mounting power supply
CPS-PWD-90AW24-01: Fitting power supply 90W
(Input: 100 - 240VAC, Output: 24VDC 3.8 A)
CPS-PWD-30AW24-01: Fitting power supply 30W
(Input: 100 - 240VAC, Output: 24VDC 1.3 A)
* Information about the option products, see the Contecs website.
Component Name
No.
Name
Function
1
Stack Bus
Used for power supply and communication with the configurable type
module.
2
LED Indicator
This indicates status of the product.
3
ZCT Connector
Used to connect the ZCT unit. (use ZCT unit included in the package)
4
Voltage Measurement
Connector
Used to measure voltage. (use the 4-pin connector included in the
package)
25.2
124.8
(14)
(18)
φ4
φ4
(14)
(18)
[mm]
94.7
5.1