Classification
NAPOPC_CE5 FAQ
No.
1-006-E
Author
James
Version
1.0.0
Date
2010/7/12
Page
1/5
ICP DAS Co., Ltd. Technical document
How to use FRnet modules in NAPOPC_CE5
If you want to exchange data between WinPAC/ViewPAC and FRnet modules, you have to plug
I-8172W in your WinPAC/ViewPAC, so as to communicate with FRnet modules.
Before operating, let’s clarify Receiver Address and Sender Address:
On the manual of FRnet DI modules, it may just show the ”Sender Address” is between 8 to 15.
However, In NAPOPC, we have to set ”Receiver Address” the same as the ”Sender Address” of
FRnet DI modules.
Actually, “sender” and “receiver” have opposite relationship. For example, FRnet DI module gets
a DI signal, and “send” it to NAPOPC. In this situation, NAPOPC plays the role of “receiver”. On
the contrary, we “send” command from NAPOPC to the DO module, and the role of DO module
is “receiver”. Please follow this rule to set FRnet modules in NAPOPC.
FRnet modules are not supported by “Search” function, you can only add FRnet modules
manually:
Step 1 Add FRnet DI module (Example: FR-2053)
Click “Device” on the Toolbar to add new device.
Platform
OS version
NAPOPC version
WinPAC / ViewPAC
CE5
NAPOPC_CE5 v2.20
Classification
NAPOPC_CE5 FAQ
No.
1-006-E
Author
James
Version
1.0.0
Date
2010/7/12
Page
2/5
ICP DAS Co., Ltd. Technical document
It will show you the dialog as below:
After setting up, just click ”OK”.
FRnet module
Slot of I-8172W and the Port you use
Module name
Receiver Address, must be the same as
Sender Address of the FRnet DI module
Slot