Pressure to Current
Transducer
VALVES
517
Electro-Pneumatic Transducer
Low Cost, Selectable Input/Output, Manual Override
Series
EPTA
The Series EPTA is an electric to pneumatic transducer that converts an analog input
signal to a linearly proportionate pneumatic output by modulating its control valves to
regulate branch line pressure to the set point determined by the input signal. All models
incorporate two low voltage valves, an integral in-barb filter, a 0 to 30 psi analog gauge, an
anodized aluminum manifold, and brass barbed fittings. The EPTA offers adjustable span
and offset as well as manual override. This unit has no air consumption and is immune to
mounting orientation. Output pressure ranges include field-selectable 0 to 10, 0 to 15, and
0 to 20 psig. Also included is an analog 0 to 5 VDC feedback signal indicating the resultant
branch line pressure. Universal 24 VAC/24 VDC supply voltage and field-selectable 4 to 20
mA, 0 to 5 VDC, 0 to 10 VDC, or 0 to 15 VDC inputs ensure single unit compatibility with
most systems. The standard models maintain branch pressure on power loss while the Fail-
Safe models will drop the branch pressure to 0 psi on power loss. Mounting configurations
include a metal bracket mount in the EPTA-B models and a snap-track mount in the EPTA-
S models. The A-400 accessory kit will allow the EPTA-S models to be mounted on a
standard DIN rail.
SPECIFICATIONS
Service: Clean dry air or any inert gas.
Input Signal: DC current (4 to 20 mA) or DC voltage (0-5/0-10/0-15).
Input Impedance: Current: 250 Ω; Voltage: Infinite.
Output Signal: Jumper selectable 0 to 10 psig (0 to 69 kPa), 0 to 15 psig (0 to 103
kPa), or 0 to 20 psig (0 to 138 kPa).
Feedback Output: 0 to 5 VDC.
Air Supply: 25 psig (172 kPa) max.
Air Flow: 750 scim.
Air Consumption: 0 scim normal operation, fail-safe model vents to 0 psi on
power loss.
Accuracy: ±1.0% full-scale @ room temperature; ±2.0% full-scale @ 32 to 120°F
(0 to 48.8°C).
Supply Voltage: 24 VDC (+10%/-5%) or 24 VAC (±10%) 50/60 Hz.
Supply Current: 180 mA max, 200 mA max on fail-safe model.
Temperature Limits: Operating: 32 to 120°F (0 to 48.8°C); Storage: -20 to 150°F
(-6.7 to 65.6°C).
Operating Humidity Range: 5 to 95%, non-condensing.
Pressure Connections: 1/4˝ OD (polyethylene tubing optimum).
Electrical Connections: Plug-in block terminal type with 5 mm pin spacing.
Wire Size: Up to one 14 AWG per terminal.
Weight: EPTA-S0: 6.9 oz. (196 g); EPTA-S1: 9.2 oz. (261 g); EPTA-B: 14.5 oz.
(411 g).
Model
EPTA-S0
EPTA-B0
EPTA-S1
EPTA-B1
POWER
MANUAL
AUTO
MANUAL
0% 100%
SPAN
OFFSET
10V
15V
20mA
0-10 PSI
0-15 PSI
0-20 PSI
5V
4X ø13/64
[ø5.16]
3-23/64
[85.33]
1-23/64
[34.53]
23/64
[9.13]
4-1/16
[103.19]
4-5/16 [109.54]
3-25/64 [86.12]
4-15/32
[113.5]
PWR C SIG FB OV OV
3/16
[4.76]
23/32
[18.26]
1/2
[12.7]
27/32
[21.43]
3-27/64
[86.92]
3-1/4
[82.55]
3 [76.20]
3-1/4 [82.55]
23/32
[18.26]
PWR C Sig FB OV OV
EPTA-S
EPTA-B Shown with snap-track mounting
Shown with metal bracket mounting
The Model PI Pressure To Current Transducer converts a pneumatic input pressure
to an accurately proportional output current with uncompromising accuracy and durability.
The PI serves in high-density and panel-mounted applications. The rugged PI transducer
offers a high density DIN rail adapters and space saving with easy plug-in installation.
Pressure To Current Transducer
Reliable, User-Oriented Performance
Model
PI
Model
PI-1
PI-2
17/32
[13.46]
3
[76.20]
1-63/64
[50.47]
3/4
[19.05]
5/16
[7.75]
1
[25.40]
PRESSURE INLET
1/8˝ NPT
3
[76.20]
3/4
[19.02]
3-7/16
[87.12]
45/64
[17.78]
5-25/32
[146.84]
5-3/8
[136.66]
MODEL NO. PI-X
SUPPLY: 10-42 VDC
MAX. TEMP: 75°C
INPUT:X-XX PSIG
OUTPUT: 4 TO 20 mA
SERIAL NO: XX-XXXX
TAG NO: XXX-XXXX
W.E. ANDERSON
A DIV OF DWYER INSTRUMENTS, INC
MICHIGAN CITY, IN USA
SPECIFICATIONS
Service: Clean dry air filtered to 40
microns.
Input Signal: 3 to 15 psig and 3 to 27
psig.
Input Capacitance: 2-wire: 700 ƒ,
standard; Voltage: 5k ƒ min.
Output: 2-wire: 4 to 20 mA.
Linearity: ±0.15% of span.
Hysteresis: ±0.15% of span max.
Accuracy: ±0.15% of span
guaranteed; ±0.10% of span typical.
Includes combined effects of linearity,
hysteresis and repeatability errors.
Repeatability: ±0.10% of span;
±0.03% of span typical.
Response Time: 10 ms to 99% of step
change.
Power Requirements: 10 to 42 VDC.
Temperature Stability: Span and
Zero: ±0.007% of span per °F max.
deviation from 77°F calibration.
Temperature Limits:
Operating: -40 to 167°F (-40 to 75°C);
Storage: -60 to 185°F (-50 to 85°C).
Calibration Adjustments: Non-
interactive, multi-turn span and zero
potentiometers with approximately
±10% of span adjustment range.
Connections:
Signal Air: 1/8˝ NPT female;
Electrical Wiring: Miniature terminal
block accepts solid or stranded wire
up to 14 AWG.
Weight: 0.5 lb (0.2 kg).
CONTACT US | U.S. 219/879-8000 | U.K. (+44) (0)1494-461707 | A.U. (+61) (0) 2 4272 2055 | China +852-23181007
ACCESSORIES
A-400, DIN Mounting Kit
A-403, Replacement Integral Barb Filter
Description
Standard Snap-Track Mount Transducer
Standard Metal Bracket Mount Transducer
Snap-Track Mount Transducer with Fail-Safe
Metal Bracket Mount Transducer with Fail-Safe
Range
3 to15 psig (20 to 100 kPa)
3 to 27 psig (20 to 180 kPa)
PI-C, Replacement DIN Rail Adapter
517_Layout 1 7/8/14 9:22 AM Page 517