DESIGN & CONSTRUCTION
CONDUCTOR
Class B compact concentric soft drawn
copper from #2 AWG through 1000 kcmil
multiconductor
CONDUCTOR SHIELD
Extruded thermosetting semiconducting
shield which is free stripping from the
conductor and bonded to the insulation
INSULATION
High dielectric strength EPROTENAX®
EPR- based insulation, combined with
other additives that enhance the electrical
and mechanical characteristics and
extending cable life
INSULATION SHIELD
Extruded thermosetting semiconducting
shield with controlled adhesion to
the insulation providing the required
balance between electrical integrity and
strippability
METALLIC SHIELD
Helically applied non-magnetic copper
tape(s) over the insulation shield with a
minimum overlap of 15%. A Mylar ribbon
is applied longitudinally under the copper
tape shield for phase identification
1C w/ Red, 1C w/ Blue, and 1C w/ Black
OUTER SHEATH
Sunlight, oil, and moisture resistant PVC
meeting the requirements of CSA 22.2
No. 03 -40/-35 °C Cold bend/Cold impact
Oil & Gas - Cable Solutions
ICEA S-93-639 (NEMA WC74)
Pipelines & LNG - Onshore
Medium Voltage Cables
MV-105 POWER 5-35 kV EPR
Cu/Semicon/EPR/Semicon/Cu Tape/PVC
Medium Voltage power cables 5-35 kV. Flame retardant,sunlight resistant, PVC jacket.
APPLICATION
Medium Voltage single conductor MV-105
power cables are designed to deliver power in
fixed installations in industrial facilities. Cables
may be installed in wet or dry locations in duct,
cable trays, directly buried. or installed on
messenger. Cables are rated sunlight resistant
and are listed for CT use.
STANDARDS & APPROVALS
ASTM B3 & ASTM B8 (Conductors)
ICEA S-93-639 (NEMA WC74)
ICEA S-97-682
UL 1072
AEIC CS8
IEEE 383 (#1/0 AWG and larger)
UL 1202 (250 kcmil and larger)
CSA C68.10
CSA 96.1
CSA 22.2 No. 03 (Cold Bend/Cold Impact)
MSHA (Mine Safety & Health Administration)
1
2
3
4
5
6
1
2
3
4
5
6
CONTACT INFO:
prysmianoilandgas@prysmiangroup.com
www.prysmiangroup.com/contact-us
2
P/L MV-105 - 09/2017
This product information sheet is provided for reference only.
Please consult the factory or your representative to confirm all engineering information or refer to the related catalogues available in the local countries website.
QUALITY & TESTING
Prysmian has a built-in multi-step quality assurance program, covering the production process from cable design and raw material
purchases to final inspection and testing documentation.
The ISO 9001 quality system of Prysmian Group (together with ISO 14001 and OHSAS 18001) has been assessed, approved and is currently
audited by SGS.
PERFORMANCES/RATINGS
VERY GOOD
CHEMICAL
RESISTANCE
IEEE 1202/ FT4 (250 kcmil and larger)
IEEE 383 (#1/0 AWG and larger)
FIRE
BEHAVIOUR
GOOD
IMPACTS
low
LOW EMISSION
SMOKE DENSITY,
CORROSIVITY
AND TOXICITY
+105 °C
MAX
OPERATING
TEMPERATURE
Cold bend / Cold impact
-40 °C / -35 °C
MIN.
INSTALLATION
TEMPERATURE
250
°C
+250 °C
SHORT
CIRCUIT
TEMPERATURE
+140 °C
EMERGENCY
OVERLOAD
TEMPERATURE
Oil & Gas - Cable Solutions
ICEA S-93-639 (NEMA WC74)
Pipelines & LNG - Onshore
Medium Voltage Cables