Pressure sensor
SPAU-B2R-H-G18FD-L-PNLK-PNVBA-M8U
Part number: 8001219
Data sheet
Feature Value
Type code SPAU
Electrical connection 1, connection technology M8x1 A-coded as per EN 61076-2-104
Electrical connection for input 1, connection pattern 00991171
KC characters KC EMC
Electrical connection 1, connection type Plug
Electrical connection 1, number of pins/wires 4
Symbol 00995410
Certification RCM compliance mark
c UL us - Listed (OL)
CE marking (see declaration of conformity) As per EU EMC directive
As per EU RoHS directive
Note on materials RoHS-compliant
Measured variable Relative pressure
Method of measurement Piezoresistive pressure sensor
Pressure measuring range initial value -1 bar
Pressure measuring range end value 1 bar
Max. overload pressure 5 bar
Operating medium Compressed air as per ISO 8573-1:2010 [7:4:4]
Inert gas
Information on operating and pilot media Operation with oil lubrication possible
Temperature of medium 0 °C ... 50 °C
Ambient temperature 0 °C ... 50 °C
ADC resolution 12 bit
Accuracy in ± % FS 1.5 %FS
Repetition accuracy in ± %FS 0.3 %FS
Temperature co-efficient in ± %FS/K 0.05 %FS/K
Switching output 2 x PNP or 2 x NPN switchable
Switching function Freely programmable
Switching element function N/C contact/N/O contact switchable
Max. output current 100 mA
Analog output 1 - 5 V
0 - 10 V
4 - 20 mA
Rise time 3 ms
Max. load resistance of current output 500 Ohm
Min. load resistance of voltage output 10 kOhm
Short-circuit protection yes
4/29/20 - Subject to change - Festo AG & Co. KG 1/2
Feature Value
Protocol IO-Link®
IO-Link®, protocol version Device V 1.1
IO-Link®, profile Smart sensor profile
IO-Link®, function classes Process data variable (PDV)
Diagnostics
Teach channel
Binary data channel (BDC)
Identification
IO-Link®, communication mode COM2 (38,4 kBd)
IO-Link®, SIO mode support Yes
IO-Link®, port class A
IO-Link®, process data width OUT 0 Byte
IO-Link®, process data width IN 2 Byte
IO-Link®, process data content IN 14 bit PDV (pressure measurement)
2 bit BDC (pressure monitoring)
IO-Link®, minimum cycle time 3 ms
IO-Link®, data memory required 500 byte
DC operating voltage range 20 V ... 30 V
Reverse polarity protection for all electrical connections
Type of mounting With H-rail
Mounting position Any
Pneumatic connection G1/8
Product weight 70 g
Display type Illuminated LCD
Displayable unit(s) kgf/cm²
kPa
MPa
bar
inchHg
mmHg
inchH2O
psi
Setting options IO-Link®
Via display and pushbuttons
Teach-in
Protection against tampering IO-Link®
PIN code
Threshold value setting range 0 % ... 100 %
Hysteresis setting range 0 % ... 90 %
Degree of protection IP65
IP67
Corrosion resistance class (CRC) 2 - Moderate corrosion stress
4/29/20 - Subject to change - Festo AG & Co. KG 2/2