PS3500 Power Supply Backplane - 6-position
90 - 250 V AC
90 - 300 V DC
24 V DC
Zone 2
Div. 2
Connection
Assembly
6-position backplane for PS2500/PS3500 series power
modules
Multiple input/output wiring configurations
Removable terminals for easy wiring
Serial or parallel fault bus
ATEX, IECEx, and cULus approvals for Div 2/Zone 2
Function
The PS3500-TB-6 is a 6-position backplane used by the
PS2500/PS3500 series power supply modules. Power
configuration and alarms are controlled by DIP switches on the
backplane. The backplane connects to universal AC (90-250
V) or DC (90-300 V) inputs and supports redundancy.
The PS3500-TB-6 allows a maximum of 90 A of output power,
75 A in N+1 configuration or 45 A in triple redundant mode.
Automatic load sharing of all of the power modules is built into
the backplane. Input and output lines can be wired
independently or in parallel, providing easy configuration of
N+1 redundancy.
The fault bus can be configured in serial or parallel
combinations.
Features
Release date 2017-02-28 19:20 Date of issue 2017-02-28 911113_eng.xml
Technical data PS3500-TB-6
2
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
Pepperl+Fuchs Group USA: +1 330 486 0002 Singapore: +65 6779 9091Germany: +49 621 776 2222
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
Interface
Type diagnostic bus: RS 485
Input
Rated values terminal ratings: current 6.5 A per slot
Voltage 90 ... 250 V AC, 44 ... 66 Hz; 90 ... 300 V DC
Output
Rated values terminal ratings: current 65 A, voltage 300 V
Fault signal removable terminals : power module alarm
Indicators/settings
Control elements DIP switches for alarm and load sharing configuration
potentiometers for output voltage adjustment
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EU Refer to DoC for all directives and standards met.
Conformity
Electromagnetic compatibility NE 21:2006
Degree of protection EN 60529
Shock resistance EN 60068-2-27
Vibration resistance EN 60068-2-6
Ambient conditions
Ambient temperature -25 ... 70 °C (-13 ... 158 °F)
Storage temperature -40 ... 85 °C (-40 ... 185 °F)
Relative humidity < 95 % , noncondensing
Shock resistance 15 g , 11 ms
Vibration resistance 1 g , 58 ... 150 Hz
Mechanical specifications
Core cross-section input terminals: 4 mm
2
(10 AWG)
output terminals: 10 mm
2
(6 AWG)
Housing material Powder Coated, 1010 Cold Rolled Steel
Degree of protection IP20
Mass approx. 2.9 kg ( 6.375 lbs )
Dimensions 193 x 78 x 486 mm (7.6 x 3.1 x 19.1 inch)
Data for application in connection
with hazardous areas
Certificate DEMKO 12 ATEX 1103387X
Marking ¬ II3 G Ex nA IIC T4 Gc
International approvals
UL approval cULus Listed
E230669
E350173
Approved for Class I/Div 2, ABCD
Class I, Zone 2, Grp IIC T4
IECEx approval IECEx UL 13.0082X
Ex nA nC IIC T4 Gc
General information
Supplementary information Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be
observed where applicable. For information see www.pepperl-fuchs.com.