1
1.0 GENERAL INFORMATION
Every Model 809 has been tested and calibrated before shipment.
Gems Sensors 809 pressure transducers sense gauge pressure and convert this
pressure difference to a proportional high level analog output. Three standard
output and excitation versions are offered:
Excitation Output
9 to 28 VDC 4 to 20 mA - (Must Observe Polarity)
9 to 30 VDC 0.5 to 5.5 VDC - (Reverse excitation protection)
4.9 to 8.1 VDC 0.5 to 4.5 VDC - (No reverse wire protection)
2.0 MECHANICAL INSTALLATION
2.1 Media Compatibility
Model 809 transducers are designed to be used with any gases or liquids
compatible with 17-4 PH Stainless Steel.
2.2 Environment
The operating temperature limits of the 809 are -40° to +185°F (-40 to +85°C).
The compensated temperature range is -4 to +176°F (-20 to +80°C).
2.3 Pressure Fittings
Typically, standard pipe fittings and procedures should be used. However, for
pressure ranges in excess of 500 psig, we suggest the use of a sealant such as
Loctite Hydraulic Sealant. Excessive torquing of metal fittings may cause a
slight zero shift. The use of plastic fittings typically results in no noticeable zero
shift. Torquing does not appreciably affect linearity or sensitivity.
2.4 Tube Stub Welding Instructions
Standard welding practices should be followed. Caution must be taken to
protect the sensor against current paths that could damage the circuit board.
Apply a heat sink between the weld zone and the sensor that is large enough
to protect the sensor from overheating. Failure to use a heat sink may damage
the housing seal or circuit board.
2.5 Venting
Because the reference pressure in a sealed gage transducer will vary due to
changes in temperature and will affect overall accuracy (especially in units of
less than 500 psig range), all 809 Series transducers are available as vented or
sealed to atmosphere.
Vented units are ordered as PSIG range units. Sealed units are ordered as PSIS
range units. The 809 PSIG transducers are vented through the cable.
Hirschmann PSIG transducers are vented through the connector. Packard
PSIG units are vented through a porous filter plug supplied on the unit.
3.0 ELECTRICAL INSTALLATION
The Model 809 is available in four electrical terminations:
2 foot Cable Hirschmann Connector
Packard Connector Conduit Adapter, 1/2 inch
Gems Sensors 809 Series
Pressure Transducer
Instruction Bulletin No. 203022
4
SS2114 Rev. A 01/03
RETURN POLICY
Returns are accepted on stock items up to 30 days from date of order.
You must contact our Returns Department for a Return Authorization
(RA) number. Return the goods - freight prepaid - in the original
container and include original packing slip. C. O. D. returns are not
accepted. Gems reserves the right to apply restocking charges.
Tel: 860-793-4357
Fax: 860-793-4563
Gems Sensors
One Cowles Road
Plainville, CT 06062-1198
Toll-Free: 1-800-378-1600
Gems products must be maintained and installed
in strict accordance with the National Electrical
Code and the applicable Gems Product Instruction
Bulletin that covers installation, operating and
proper maintenance. Failure to observe this
information may result in serious injury or
damages.
Please adhere to the pressure and temperature
limitations shown throughout this bulletin. These
limitations must not be exceeded. These pressures
and temperatures take into consideration possible
system surge pressures/temperatures and their
frequencies.
Important Points
Selection of materials for compatibility with the
media is critical to the life and operation of Gems
products. Take care in the proper selection of
materials of construction, testing is required.
Our sensors have been designed to resist shock and
vibration. However, shock and vibration should be
minimized.
Our sensors must not be field-repaired.
Physical damage sustained by product may render it
unserviceable.
2
3.2 Current Output Units
The Model 809 (current output) transducer is a true 2-wire, 4-20 mA current
output device and delivers rated current into any external load of 0-800 ohms.
The 4-20 mA units are designed to have current flow in one direction only -
PLEASE OBSERVE POLARITY. We suggest that the electrical cable shield be
connected to the systems loop circuit ground to improve electrical noise
rejection. The electrical connection is as follows:
Red + Excitation
Black - Excitation
+
Monitor or
Control
Device
_
Green
+ Out
White
- Out
Shield
3.3 Hirschmann or Packard Connectors - Voltage and Current Output
If the unit is provided with a Hirschmann or a Packard Connector, pin number
designations are as follows:
3.1 Voltage Output Units
The Model 809 voltage output is a 3-wire circuit. If the 809 is supplied with 2 feet of
cable, the electrical connection is as follows:
Red =
+ Excitation; connect to appropriate power supply.
Green =
+ Output; connect to controls or monitor.
Black =
Common; connect to return of power supply.
White =
- Output; connect to controls or monitor.
Shielding =
Connect to system or earth ground.
-Out White
+Out Green
Hirschmann Connector
3-Pin Packard Connector
Top View: 3-Pin Packard Connector
Type: P2S Series 150
Voltage Output
Pin # Function
1+ Excitation
(connect to appropriate power supply)
3+ Output (connect to controls or monitor)
2Common (connect to return of power supply)
2
3
1
Top View: Hirschmann Connector
Type: G4A1M#931807-106
Pin # Function
1Positive
2Negative
Current Output
Voltage Output
Pin # Function
B + Excitation (connect to appropriate power supply)
C + Output (connect to controls or monitor)
A Common (connect to return of power supply)
A
B
C
Pin # Function
BPositive
ANegative
Current Output
The 809 has a 2-wire cable, where red is positive and black is negative.
CAUTION: Reverse excitation will not cause damage to unit unless voltage
applied is above 50 VDC. However, unit will not function if reverse wired.
Model 809
Gems Transducer
(4-20 mA)
Power
Supply
Load
(Monitor)
+
+
+
_
__
Red
Black
CAUTION: Unit is reverse excitation protected. However, do not
apply power to output lead as this could cause permanent damage.
3
3.4 Conduit Adapter Electrical Termination - Voltage and Current
Output Units
If the unit is provided with the conduit adapter version, terminal designations
are as follows:
Conduit Adapter Version
(Voltage and Current Output Units)
For current (4-20 mA)
output, use + and -
terminals
For voltage output, use
COM, OUT and EXC
terminals
4
1. Connect the pressure port to the system.
2. Install a 1/2’ conduit fitting into the 809 top cover, and fasten the retaining nut.
3. Feed wires from a flexible conduit through the 809 top cover, fasten the wires to terminals.
4. Screw on the Model 809 top cover.
5. Fit conduit into conduit fitting, and tighten conduit watertight strain relief.
A
B
C
D
CONDUIT FITTING INSTALLATION INSTRUCTIONS
4-Pin Packard Connector
Gems does not supply the mating connectors as a standard. They can be ordered
separately. Consult Factory
Pin # Function
APositive
BNegative
Top View: 4-Pin Packard Connector
Type: Metri-Pack 150
Current Output
Voltage Output
Pin # Function
A + Excitation (connect to appropriate power supply)
C + Output (connect to controls or monitor)
B Common (connect to return of power supply)
D (Not Used)
Vent
2
1
3
2
4
5
3.6 EMC Certification
This product complies with EN61326 Electrical Equipment for Measurement, Control and
Laboratory use – EMC Requirements for Minimum Requirements and Industrial Locations.
Special caution should be taken to meet Standard EN61000-4-5: 1995 Surge Immunity if
any of the following conditions apply to the installation: The product is installed outside;
all or any part of the cable is exposed to the outside; the cable is greater than 30 meters in
length. In order to meet the Surge Immunity requirements, the following conditions must
be followed during installation:
1. Shielded cable must be used, and the shield must be tied to earth ground (not power supply
ground) on at least one end of the cable shield/drain wire. The shield must be maintained all
the way from sensor to the power supply.
2. If unshielded cable is used, an earth grounded metal conduit fitting can be used to replace the
shielded cable.
3. For a sensor with a metal body or enclosure, the body/enclosure must be grounded to earth. If
a protective metal housing is used, the metal housing should be grounded to earth
4. If a protective plastic housing is used, the housing must be able to withstand at least
2 KV from the housing to earth ground, without damaging the circuit.
3.5 Conduit Fitting Installation