In combination with the Teleflex VX, the system can
be used for ARM® Burning. This method allows high
resistance faults to be located while completing a fault
conversion.
Additionally, the system provides a sheath fault pinpointing
function with clocked DC voltage.
The user is guided through the location process using the
proven easyGO control system.
DESCRIPTION
The BPS 5000-C is usually built into cable fault location
systems, but can also be used as a portable device for
fault converting or burning. In basic operations the digital
control unit, can be used as a burner for cable faults that
are difficult to locate, and as a control device for external
test systems. With this external test system you can carry
out conventional DC tests or the long-established and
norm-compliant VLF cable test using the VLF 0.1 cosine
rectangular wave form.
The leakage current is recorded during the VLF test, which is
a special feature of the cosine rectangular wave form.
All essential measurements can be logged and transferred
by using the integrated USB connection.
Control for AC-, DC- and VLF testing
ARM® burning
DC testing up to 110kV
Burning up to 110A
VLF testing up to 54kV / 5uF
Integrated Sheath fault location
BPS 5000-C
Burn and proof test system for medium
voltage cables
SALES OFFICE
Megger Germany GmbH
Dr.-Herbert-Iann-Str. 6,
D-96148 Baunach
T +49 9544 68-0
E team.international@megger.com
BPS5000-C_DS_EN_V02
www.megger.com
ISO 9001
The word ‘Megger’ is a registered trademark
TECHNCAL DATA*
Fault conversion
Voltage/Current 0 … 1,2 kV
DC
6.0 A
4 kV
DC
1.5 A
8 kV
DC
0.8 A
15 kV
DC
0.5 A
0 ... 60 V
AC
110 A
0 ... 240 V
AC
28 A
DC test (with optional DC testing)
Voltage/Current 0 … 80 kV, I
N
15 mA, I
max
50 mA
or
0 … 110 kV, I
N
7 mA, I
max
50 mA
Output power 1.5 kVA
Short circuit power 3.5 kVA (max. 1 h)
AC test
Voltage 58 kV
AC
VLF – testing according to DIN VDE 0276
Voltage 0 … 54 kV
eff
Max. load 21 μF at 18 kV
eff
@ 0.1 Hz
8 μF at 36 kV
eff
@ 0.1 Hz
5 μF at 54 kV
eff
@ 0.1 Hz
Nominal current 15 mA +/- 3 mA
Input power 1 kVA
Sheath fault location
Output voltage 0 … 10 kV
Output current 800 mA (up to 5 kV)
500 mA (up to 10 kV)
Clock 1:3
General
Display LCD, resolution 320 x 240
Operating - 10 °C + 40 °C
Temperature range Software controlled shutdown @ 120 °C
Hardware controlled shutdown @ 145 °C
Input voltage 230 V +/- 10 %, 45 … 60 Hz
Power consumption Max. 7 kVA
Protection class IP 20
Safety class I
* We reserve the right to make technical changes.
BPS 5000-C
Burn and proof test system for medium
voltage cables