Document No. D189-00-001-IS Issue: 10 04-12-19 Sheet 1 of 7
INSTRUCTION & SERVICE MANUAL
D2xS1 ALARM HORN
For Use In Hazardous Locations
1) Introduction
The D2xS1 is an ATEX, IECEx and UL certified alarm horn
which produces a loud warning signal in a hazardous area.
Sixty-Four first stage alarm sounds can be selected by internal
switches and each one can be externally changed to a second,
third or fourth stage alarm sound. The alarm horn may be used
for Gas applications in Zone 2 / Class I Zone 2 / Class I,
Division 2 as well as for Dust applications in Zone 22 / Class II
Zone 22 / Class II Division 2 / Class III Division 1 & 2. A D2xC1
combined alarm horn & strobe is also available. The 24Vdc
version is also listed for use in fire alarm systems public
mode in accordance with UL464 Tenth Edition / CAN/ULC-
S525 Fourth Edition.
2) Warnings
SUITABLE FOR USE IN CLASS II, DIVISION 2, GROUPS A, B, C
AND D HAZARDOUS LOCATIONS
SUITABLE FOR USE IN CLASS II, DIVISION 2, GROUPS E, F AND G
HAZARDOUS LOCATIONS
WARNING: DO NOT OPEN WHEN EXPLOSIVE ATMOSPHERE IS
PRESENT
WARNING EXPLOSION HAZARD SUBSTITUTION OF ANY
COMPONENT MAY IMPAIR SUITABILITY FOR CLASS I, DIVISION 2.
WARNING EXPLOSION HAZARD SUBSTITUTION OF ANY
COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS II, DIVISION
2.
POTENTIAL ELECTROSTATIC CHARGING HAZARD CLEAN
ONLY WITH A DAMP CLOTH
USE HEAT RESISTANT CABLES AND CABLE GLANDS (RATED
90ºC OR HIGHER)
EXPLOSION HAZARD. DO NOT REMOVE OR REPLACE LAMPS,
FUSES OR PLUG-IN MODULES UNLESS POWER HAS BEEN
DISCONNECTED OR THE AREA IS KNOWN TO BE FREE OF
IGNITIBLE CONCENTRATIONS OF FLAMMABLE GASES OR
VAPORS.
EXPLOSION HAZARD. DO NOT DISCONNECT WHILE THE
CIRCUIT IS LIVE OR UNLESS THE AREA IS KNOWN TO BE FREE
OF IGNITIBLE CONCENTRATIONS.
DO NOT PAINT
NE PAS PEINTURER
3) Ratings and Markings
3.1 ATEX / IECEx certification
The D2xS1 alarm horn complies with the following standards:-
EN60079-0:2012 / IEC60079-0: ed. 6.0 (2011-06)
EN60079-15:2010 / IEC60079-15: ed. 4.0 (2010-01)
EN60079-31:2009 / IEC60079-31:2009 ed. 1.0 (corr. 1 2009)
The Type Examination Certificate DEMKO
14ATEX4786493904X / IECEx ULD14.0004X has been issued
by UL. This confirms compliance with the European ATEX
Directive 94/9/EC for Group II, Category 3G/D equipment. The
alarm horn carries the Community Mark and subject to local
codes of practice, may be installed in any of the EEA member
countries. This instruction sheet describes installations which
conform to the current issue of EN60079-14/IEC60079-14
Electrical Installation in Hazardous Areas; EN60079-10-1 / IEC
60079-10-1 Explosive Atmospheres - Classification of Areas.
Explosive Gas Atmospheres; EN60079-10-2 / IEC 60079-10-2
Explosive Atmospheres - Classification of Areas. Explosive
Dust Atmospheres. When designing systems for installation
outside the UK, the local Code of Practice should be consulted.
The D2X Alarm horn is rated as follows:
CE Marking
Zones, Gas / Dust Groups and Temperature Classification
When connected to an approved system the D2X alarm horn
may be installed in:
Zone 2 explosive gas air mixture not likely to occur in
normal operation, and if it does, it will only exist
for a short time.
Zone 22 explosive dust air mixture not likely to occur in
normal operation, and if it does, it will only exist
for a short time.
May be used with gases in groups:
Group IIA propane
Group IIB ethylene
Group IIC hydrogen / acetylene
Having a temperature classification
(for Gas applications) of:
T1 450ºC
T2 300ºC
T3 200ºC
T4 135ºC
May be used with Dust types:
Group IIIA combustible flyings
Group IIIB non-conductive dust
Group IIIC conductive dust
Maximum Surface Temperature for Dust Applications:
90ºC
3.2 Class / Zone ratings US
The D2xS1 alarm horn complies with the following standards:
ANSI/UL 60079-0-2013
ANSI/UL60079-15-2013
ISA60079-31-2013
The D2X Alarm horn is rated as follows:
Class I, Zone 2 AEx nA IIC T4 Gc (Ta -40ºC to +50°C)
Zone 22 AEx tc IIIC T90°C Dc (Ta -40ºC to +50°C)
II 3G Ex nA IIC T4 Gc (Ta -40ºC to +50ºC)
II 3D Ex tc IIIC T90ºC Dc (Ta -40ºC to +50ºC)
2813
__________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH sales@e-2-s.com Tel: +44 (0)208 743 8880
www.e-2-s.com Fax: +44 (0)208 740 4200
Document No. D189-00-001-IS Issue: 10 04-12-19 Sheet 2 of 7
Installation must be carried out in compliance with the National
Electric Code.
3.3 Class / Zone ratings Canada
The D2xS1 alarm horn complies with the following standards:
CAN/CSA C22.2 No. 60079-0:11
CAN/CSA C22.2 No. 60079-15:12
CAN/CSA C22.2 No. 60079-31:12
The D2XS1 Alarm horn is rated as follows:
Ex nA IIC T4 Gc X (Ta -40ºC to +50°C)
Ex tc IIIC T90°C Dc (Ta -40ºC to +50°C)
Class II Div 2 EFG T5 (Ta -40ºC to +50°C)
Installation must be carried out in compliance with the
Canadian Electric Code
3.4 Class / Division Ratings for US and Canada
The D2xS1 alarm horn complies with the following standards:-
ANSI/ISA 12.12.01-2013
CSA C22.2 No. 213-M1987
CSA C22.2 No. 157-92:2006
The D2XS1 Alarm horn is rated as follows:
Class I Div 2 ABCD T3C Ta -40ºC to +70ºC
Class I Div 2 ABCD T4 Ta -40ºC to +65ºC
Class I Div 2 ABCD T4A Ta -40ºC to +50ºC
Class II Div 2 FG T5 Ta -40ºC to +50ºC
Class II Div 2 FG T6 Ta -40ºC to +45ºC
Class III Div 1 & 2 Ta -40ºC to +50ºC
Installation must be carried out in compliance with the National
Electric Code / Canadian Electric Code
3.5 Ambient Temperature Range:
-40ºC to +70ºC (Class I Div 2 only)
-40ºC to +50ºC
3.6 Ingress Protection Ratings
The product is rated for ingress Protection as follows:
IP rating per EN60529: IP66
Type rating per UL50E / NEMA250: 4 / 4X / 3R / 13
To maintain the ingress protection rating, the two off M20 cable
entries must be fitted with suitably rated, certified cable entry
and/or blanking devices during installation.
3.7 Electrical Ratings
Part No.
Nominal
Voltage
Nominal
Current
Voltage
Range
D2xS1DC024
24Vdc
313mA
10-30Vdc
D2xS1DC048
48Vdc
181mA
38-58Vdc
D2xS1AC115
115Vac
89mA
115Vac
+/-10%
60Hz
D2xS1AC230
230Vac
52mA
230Vac
+/-10%
50Hz
3.8 Fire Alarm Ratings
The following model is approved for use as an audible signal
appliance for fire alarm use public mode (UL464) and
produces a sound pressure level above 75dB(A) at 10 feet:
D2xS1DC024
For Fire Alarm applications, the Sounder Volume must be at
the highest setting, (see volume control section).
For fire alarm use, the temporal pattern tone No. 12 as per the
tone table provided in these instructions must be selected. This
tone produces a minimum sound pressure level of:
CAN/ULC-S525: 100.4dB(A)* at 10 feet.
(*anechoic room)
UL464: 92.2dB(A)
at 10 feet.
(
reverberation room)
4) Special Conditions for Safe Use
Special Condition for safe Use as stated on the Type
Examination Certificate DEMKO 14 ATEX 4786493904X / CoC
IECEx ULD 14.0004X:
End user shall adhere to the manufacturer’s installation and
instruction when performing housekeeping to avoid the
potential for hazardous electrostatic charger during cleaning,
by using a damp cloth.
The D2xS1 is not to be mounted with the horn facing upwards
The equipment shall only be used in end use with appropriately
certified cable entry devices and blanking plugs
4.1 Installation
The product must only be installed by suitably qualified
personnel in accordance with the latest issues of the relevant
standards.
The installation of the units must also be in accordance with
any local codes that may apply and should only be carried out
by a competent electrical engineer who has the necessary
training.
The alarm horn is not to be mounted with the horn facing
upwards.
The equipment has not been assessed as a safety-related
device (as referred to by Directive 94/9/EC Annex II, clause
1.5).
The cable entry temperature may exceed +70ºC / the cable
branching point may exceed 80ºC. Therefore suitable heat
resisting cables and cable glands must be used, with a rated
service temperature of at least 90ºC.
To maintain the ingress protection rating and mode of
protection, the M20 x 1.5 cable entries must be fitted with
suitably rated, certified cable glands and/or suitably rated,
certified blanking devices during installation. If a high IP
(Ingress Protection) rating is required then a suitable sealing
washer must be fitted under the cable gland. For use in
explosive gas atmospheres a minimum ingress protection
rating of IP54 must be maintained. For use in explosive dust
atmospheres a minimum ingress protection rating of IP64 must
be maintained.