European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH sales@e2s.com Tel: +44 (0)208 743 8880
www.e2s.com Fax: +44 (0)208 740 4200
Document No. D211-00-201-IS-SC Issue F 13-12-19 Sheet 1 of 5
INSTRUCTION MANUAL
D2xB1X05 & D2xB1X10 Xenon Beacons
For use in Hazardous Locations
1) Warnings
DO NOT OPEN WHEN AN EXPLOSIVE
ATMOSPHERE IS PRESENT
DO NOT OPEN WHEN ENERGISED
POTENTIAL ELECTROSTATIC CHARGING
HAZARD - CLEAN ONLY WITH A DAMP
CLOTH
HIGH VOLTAGE SHOCK HAZARD. WAIT 5
MINUTES AFTER REMOVING POWER
BEFORE OPENING THE ENCLOSURE
DO NOT PAINT
Avertissement:
NE PAS OUVRIR UN PRESENCE
D’ATMOSPHERE EXPLOSIVE
NE PAS OUVRIR ENERGIE
DANGER POTENTIEL CHARGE
ÉLECTROSTATIQUE - NETTOYER
UNIQUEMENT AVEC UN CHIFFON HUMIDE
HAUT TENSION, RISK DE CHOC.
ATTENDEZ 5 MINUTES APRES AVOIR
DEBRANCHE L’ALIMENTATION AVANT
D’OUVRIR LA BOITIER
NE PAS PEINTURER
2) Rating & Marking Information
2.1 Fire Alarm Ratings
The Following models are certified as visual alarm devices for
private mode visual alarm devices in accordance with
UL1638 Fifth Edition / CAN/ULC-S526 Fourth Edition when
used with clear or red lens covers:
D2xB1X05DC024 / D2xB1X05DC048
D2xB1X10DC024 / D2xB1X10DC048
On-axis light output per UL1638 at 1Hz:
Model
Lens cover colour
Light output in cd
D2xB1X05DC024
clear
17.4
red
5.4
D2xB1X05DC048
clear
30
red
12
D2xB1X10DC024
clear
53.4
red
17.4
D2xB1X10DC048
clear
82
red
26
2.2 surge current ratings for use in fire alarm systems
Model
Peak Surge current
RMS surge current
D2xB1X05DC024
1.04A
437mA
D2xB1X05DC048
12.7A
1.45A
D2xB1X10DC024
0.99A
620mA
D2xB1X10DC048
14.5A
780mA
2.3 NEC & CEC Class / Division Ratings for US / Canada
The D2xB1X05 and D2xB1X10 Xenon beacons comply with
the following standards:
ANSI/ISA 12.12.01-2015
CSA C22.2 No. 213-16
The D2xB1X05DC024 Xenon Beacon is rated as follows:
Class I Div 2 ABCD T2D Ta -40°C to +50°C
Class I Div 2 ABCD T3 Ta -40°C to +45°C
Class II Div 2 FG T6 Ta -40°C to +50°C
Class III Div 1&2 Ta -40°C to +50°C
The D2xB1X10DC024 Xenon Beacon is rated as follows:
Class I Div 2 ABCD T1 Ta -40°C to +50°C
Class I Div 2 ABCD T2 Ta -40°C to +45°C
Class II Div 2 FG T4A Ta -40°C to +50°C
Class II Div 2 FG T5 Ta -40°C to +45°C
Class III Div 1&2 Ta -40°C to +50°C
The D2xB1X05DC048 & D2xB1X05AC Xenon Beacons are
rated as follows:
Class I Div 2 ABCD T3 Ta -40°C to +50°C
Class II Div 2 FG T5 Ta -40°C to +50°C
Class II Div 2 FG T6 Ta -40°C to +40°C
Class III Div 1&2 Ta -40°C to +50°C
The D2xB1X10DC048 & D2xB1X10AC Xenon Beacons are
rated as follows:
Class I Div 2 ABCD T2B Ta -40°C to +50°C
Class II Div 2 FG T5 Ta -40°C to +50°C
Class II Div 2 FG T6 Ta -40°C to +40°C
Class III Div 1&2 Ta -40°C to +50°C
Installation must be carried out in compliance with the
National Electric Code / Canadian Electric Code
2.4 NEC Class / Zone ratings US
The D2xB1X05 and D2xB1X10 Xenon beacons comply with
the following standards:
UL 60079-0-2013
UL 60079-15-2013
UL 60079-31-2015
The D2xB1X05DC024 Xenon Beacon is rated as follows:
Class I Zone 2 AEx nA IIC T2 Gc Ta -40°C to +50°C
Zone 22 AEx tc IIIC 80°C Dc Ta -40°C to +50°C
The D2xB1X10DC024 Xenon Beacon is rated as follows:
Class I Zone 2 AEx nA IIC T1 Gc Ta -40°C to +50°C
Zone 22 AEx tc IIIC 105°C Dc Ta -40°C to +50°C
_______________________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH sales@e2s.com Tel: +44 (0)208 743 8880
www.e2s.com Fax: +44 (0)208 740 4200
Document No. D211-00-201-IS-SC Issue F 13-12-19 Sheet 2 of 5
The D2xB1X05DC048 & D2xB1X05AC Xenon Beacons are
rated as follows:
Class I Zone 2 AEx nA IIC T3 Gc Ta -40°C to +50°C
Zone 22 AEx tc IIIC 95°C Dc Ta -40°C to +50°C
The D2xB1X10DC048 & D2xB1X10AC Xenon Beacons are
rated as follows:
Class I Zone 2 AEx nA IIC T2 Gc Ta -40°C to +50°C
Zone 22 AEx tc IIIC 95°C Dc Ta -40°C to +50°C
Installation must be carried out in compliance with the
National Electric Code.
2.5 CEC Class / Zone ratings Canada
The D2xB1X05 and D2xB1X10 Xenon beacons comply with
the following standards:
CAN/CSA C22.2 No. 60079-0:2015
CAN/CSA C22.2 No. 60079-15:2016
CAN/CSA C22.2 No. 60079-31:2015
The D2xB1X05DC024 Xenon Beacon is rated as follows:
Ex nA IIC T2 Gc X Ta -40°C to +50°C
Ex tc IIIC 80°C Dc Ta -40°C to +50°C
The D2xB1X10DC024 Xenon Beacon is rated as follows:
Ex nA IIC T1 Gc X Ta -40°C to +50°C
Ex tc IIIC 105°C Dc Ta -40°C to +50°C
The D2xB1X05DC048 & D2xB1X05AC Xenon Beacons are
rated as follows:
Ex nA IIC T3 Gc X Ta -40°C to +50°C
Ex tc IIIC 95°C Dc X Ta -40°C to +50°C
The D2xB1X10DC048 & D2xB1X10AC Xenon Beacons are
rated as follows:
Ex nA IIC T2 Gc X Ta -40°C to +50°C
Ex tc IIIC 95°C Dc Ta -40°C to +50°C
Installation must be carried out in compliance with the
Canadian Electric Code
2.6 ATEX / IECEx certification
The D2xB1X05 and D2xB1X10 xenon beacons comply with
the following standards:
EN60079-0:2012+A11:2013 / IEC60079-0: ed. 6.0 (2011-06)
EN60079-15:2010 / IEC60079-15: ed. 4.0 (2010-01)
EN60079-31:2014 / IEC60079-31:2013 ed. 2.0 (2013-11)
Certificate No. DEMKO 14 ATEX 4786493904X
IECEx ULD 14.0004X
The D2xB1X05DC024 Xenon Beacon is rated as follows:
The D2xB1X10DC024 Xenon Beacon is rated as follows:
The D2xB1X05 Xenon Beacon is rated as follows:
The D2xB1X10 Xenon Beacon is rated as follows:
CE Marking
Zones, Gas / Dust Groups and Temperature
Classification
When connected to an approved system the D2X alarm horn
may be installed in:
Zone 2 explosive gas air mixture not likely to occur
in normal operation, and if it does, it will only exist
for a short time.
Zone 22 explosive dust air mixture not likely to occur
in normal operation, and if it does, it will only exist
for a short time.
May be used with gases in groups:
Group IIA propane
Group IIB ethylene
Group IIC hydrogen / acetylene
Having a temperature classification
(for Gas applications) of:
T1 450ºC
T2 300ºC (Excluding D2xB1X10DC024)
T3 200ºC (D2xB1X05DC048 & D2xB1X05AC only)
May be used with Dust types:
Group IIIA combustible flyings
Group IIIB non-conductive dust
Group IIIC conductive dust
Maximum Surface Temperature for Dust Applications:
D2xB1X05DC024 = 80°C,
All 48VDC, 115VAC & 230VAC units = 95°C
D2xB1X10DC024 = 105°C
Installation must be carried out in compliance with the latest
issue of the following standards:
EN60079-14 / IEC60079-14: Explosive atmospheres -
Electrical installations design, selection and erection
EN60079-10-1 / IEC60079-10-1: Explosive atmospheres -
Classification of areas. Explosive gas atmospheres
EN60079-10-2 / IEC60079-10-2: Explosive atmospheres
Classification of areas. Explosive dust atmospheres
2.7 Ingress Protection Ratings
The product is rated for ingress Protection as follows:
IP rating: IP66
Type rating per UL50E / NEMA250: 4 / 4X / 3R / 13
To maintain the ingress protection rating, the two off cable
entries must be fitted with suitably rated, certified cable entry
and/or blanking devices during installation.
II 3G Ex nA IIC T3 Gc Ta -40°C to +50°C
II 3D Ex tc IIIC 95°C Dc Ta -40°C to +50°C
II 3G Ex nA IIC T2 Gc Ta -40°C to +50°C
II 3D Ex tc IIIC 95°C Dc Ta -40°C to +50°C
II 3G Ex nA IIC T2 Gc Ta -40°C to +50°C
II 3D Ex tc IIIC 80°C Dc Ta -40°C to +50°C
II 3G Ex nA IIC T1 Gc Ta -40°C to +50°C
II 3D Ex tc IIIC 105°C Dc Ta -40°C to +50°C