Overview
The MGate 5217 is an industrial Ethernet gateway to bring Modbus
RTU/ASCII/TCP devices to BACnet/IP network.
Package Checklist
Before installing the MGate 5217, verify that the package contains the
following items:
1 MGate 5217 gateway
Quick installation guide (printed)
Warranty card
Optional Accessories:
DK-35A: DIN-rail mounting kit (35 mm)
Mini DB9F-to-TB Adaptor: DB9 female to terminal block adapter
DR-4524: 45W/2A DIN-rail 24 VDC power supply with universal 85
to 264 VAC input
DR-75-24: 75W/3.2A DIN-rail 24 VDC power supply with universal
85 to 264 VAC input
DR-120-24: 120W/5A DIN-rail 24 VDC power supply with 88 to
132 VAC/176 to 264 VAC input by switch
NOTE
Please notify your sales representative if any of the above
items is missing or damaged.
Hardware Introduction
LED Indicators
Name
Color
Function
PWR1
Red
Power is being supplied to the power input
PWR2
Red
Power is being supplied to the power input
RDY
Red
Steady: Power is on and the unit is booting up
Blinking: IP conflict, DHCP or BOOTP server did
not respond properly, or a relay output occurred
Green
Steady: Power is on and the unit is functioning
normally
Blinking: Unit is responding to locate function
Off
Power is off or power error condition exists
Ethernet
Amber
10 Mbps Ethernet connection
Green
100 Mbps Ethernet connection
Off
Ethernet cable is disconnected or has a short
P1, P2
Amber
Serial port is receiving data
Green
Serial port is transmitting data
Off
Serial port is not transmitting or receiving data
Reset Button
Press the Reset button continuously for 5 sec to load factory defaults:
The reset button is used to load factory defaults. Use a pointed object
such as a straightened paper clip to hold the reset button down for five
seconds. Release the reset button when the Ready LED stops blinking.