Time Delay Relays
Dedicated - HVAC
www.littelfuse.com/ta
Rev: 1-A-062316
TA SERIES
Lockout
Wiring Diagram
Description
The TA Series prevents rapid recycling of a compressor. A
lockout delay is started when the thermostat opens, or input
voltage is lost. Eliminates tripped circuit breakers or blown
fuses caused by a locked rotor during short cycling. The TA
will not allow the compressor to start when the line voltage
is low. Chatter of the compressor relay is eliminated. Because
of the fast initiate time, bounce of the thermostat will not be
transmitted to the compressor relay coil. A 30 second delay
provides anti-reversing protection for scroll compressors.
Operation (Lockout)
On initial closure of the S1, the compressor relay energizes
immediately. When S1 opens or input voltage is interrupted, a
lockout time delay is initiated. During this lockout time delay,
the compressor relay cannot be energized. The low voltage
(brownout) protection prevents energization of the compressor
when the line voltage is low.
Reset: The lockout time delay cannot be reset. After the time
delay is completed, the unit automatically resets.
Features & Benefits
FEATURES BENEFITS
Lockout delay
Prevents rapid cycling of compressor and eliminates
nuisance service calls due to blown fuse or tripped
breaker by locked rotor during short cycling
Anti-reversing protection
for scroll compressors
Extends life of equipment
Brownout protection
Timer will not allow the compressor to start during
low line voltage conditions
Encapsulated Protects against shock, vibration, and humidity
1A solid state output
No moving parts to arc and wear out. Provides up to
100 million operations under typical conditions
Accessories
P1023-6 Mounting bracket
The 90° orientation of mounting slots makes
installation/removal of modules quick and easy.
P1015-64 (AWG 14/16)
Female Quick Connect
These 0.25 in. (6.35 mm) female terminals are
constructed with an insulator barrel to provide
strain relief.
P1015-18 Quick Connect to Screw Adapter
Screw adapter terminal designed for use with
all modules with 0.25 in. (6.35 mm) male quick
connect terminals.
C103PM (AL) DIN Rail
35 mm aluminum DIN rail available in a 36 in.
(91.4 cm) length.
P1023-20 DIN Rail Adapter
Allows module to be mounted on a 35 mm DIN
type rail with two #10 screws.
Ordering Information
MODEL INPUT VOLTAGE TIME DELAY
TA12D1
12VDC
1m
TA12D2
12VDC
2m
TA24A0.5
24VAC
30s
TA24A3
24VAC
3m
TA24A5
24VAC
5m
If you don’t find the part you need, call us for a custom product 800-843-8848
L1 N
V = Voltage
S1 = Initiate Switch,
Contact, or
Thermostat
CR = Compressor Relay
(Load)
CA = Optional Cooling
Anticipator
© 2016 Littelfuse Protection Relays & Controls
Time Delay Relays
Dedicated - HVAC
www.littelfuse.com/ta
Rev: 1-A-062316
TA SERIES
Specifications
Input
Voltage 12 or 24VDC; 24VAC
AC Line Frequency 50/60 Hz
Impedance 450 Ω (anticipator by-pass)
Output
Minimum Load Current 75mA
Maximum Load Current 1A at 6C
Voltage Drop ≤ 1.25V
Time Delay
Initiate Time 16ms
Lockout Time Fixed 0.5, 1, 2, 3, or 5m
Tolerance -15% - 35%
Protection
Circuitry Encapsulated
Low Voltage Protection 20V: 24VAC/DC; 9V: 12VDC
Dielectric Breakdown ≥ 2000V RMS terminals to mounting surface
Insulation Resistance ≥ 100 M
Mechanical
Mounting Surface mount with one #10 (M5 x 0.8) screw
Dimensions H 50.8 mm (2”); W 50.8 mm (2”);
D 30.7 mm (1.21”)
Termination 0.25 in. (6.35 mm) male quick connect terminals
Environmental
Operating/Storage
Temperature -40° to 70°C / -40° to 85°C
Humidity 95% relative, non-condensing
Weight 2.4 oz (68 g)
Thermostat
Cooling Anticipator Resistor ≥ 1800 Ω
Function Diagram
LOCKOUT
L
E
V = Voltage
S1 = Initiate Switch
L = Load (CR)
E = Ready
TD = Time Delay
R = Reset