The power behind competitiveness
Delta UPSAmplon Family
RT Series
5/6/8/10 kVA, Single Phase; 15/20 kVA, Three Phase
A total solution for reliable power with high availability and performance
The Amplon RT Series 5-20kVA is an online double-conversion UPS that provides best-in-class designs in compact 2U size, high
power density, system efficiency, and versatile configurations to fulfill customers' requirements. Unity output power factor maximizes
capacity for more critical loads, while outstanding energy savings can be achieved based on the AC-AC efficiency of up to 96.5% and
99% in ECO mode. In addition, RT Series 5-20kVA UPS is the first in the market that offers standard Li-ion external battery cabinets,
which deliver better power density and sustainability. Along with the parallel capacity of up to four units, the new series is the ideal small
power UPS for mission-critical applications, such as servers, data centers, telecommunications, and manufacturing.
Availability & Flexibility
True online double-conversion topology and zero transfer time to battery provides
24/7 full-time protection
Wide input voltage range allows the UPS to operate in harsh electrical
environments and extends battery life
AC-start function allows the UPS to be switched on without connecting to a battery
Programmable load bank disconnects non-critical loads when a blackout occurs
and reserves more battery power for critical loads
Up to four units parallel capacity allows redundancy and load expansion (Apply to
5-10kVA)
Hot swappable batteries ensure continuous operation even when batteries are
being replaced
VRLA and Li-ion External Battery Cabinet (EBC) are available for scalable runtime
Extended Runtime models support flexible battery quantity for battery investment optimization. And when one battery fails, it could be
removed without replacing the entire battery string, reducing maintenance cost and efforts
The Power Distribution Box (PDB) and Maintenance Bypass Breaker (MBB), which are default to RT 5-10kVA Standard Runtime
models, enable simple configuration
The Maintenance Bypass Breaker (MBB) is optional for easy UPS replacement without powering down critical systems
The rRPP (Rack Remote Power Panel), which can be integrated with standard server racks, simplifies power output distribution and
power monitoring
Common battery configuration is supported in RT 15/20kVA parallel mode to save installation space and additional battery costs
Efficiency & Reliability
Unity output power factor guarantees no de-rating with loads and provides permanent 100% kW
Best-in-class AC-AC efficiency of up to 96.5% and 99% in ECO mode lowers energy costs
Automatic fan speed control maximizes system efficiency and significantly reduces audible noise and prolongs battery life
Fan failure detection sends early warnings to facilitate predictive maintenance of UPS
Manageability
Intelligent battery management to extend battery life and maximize battery performance. The battery aging detection monitors battery
status for predictive maintenance, and the 3-stage charging mechanism keeps the battery from continuous float charging during the
intermission stage to prolong battery life
Excellent local management through a user-friendly graphical and multi-lingual LCD display
Various types of communication interfaces, including USB, RS-232, and RS-485 ports, mini slot, REPO/ROO for remote management,
and in-built dry contacts for monitoring and notification of system operation conditions
UPS management software such as ShutdownAgent and InfraSuite Device Manager allow users to monitor UPS status and protect
critical devices
Server
Network Banking
POS
Security
$
Delta UPSAmplon Family
RT Series
5/6/8/10 kVA, Single Phase; 15/20 kVA, Three Phase
Technical Specifications
Power Rating 5kVA/5kW 6kVA/6kW 8kVA/8kW 10kVA/10kW 15kVA/15kW 20kVA/20kW
Input
Voltage Range 100 ~ 280V (Single phase, 2-wire + G)
100 ~ 175V with linear de-rating 50 ~ 100%
Frequency
40 ~ 70 Hz
Power Factor > 0.99 (full load)
iTHD
< 3%
138 ~ 485V (Three phase, 4-wire + G)
138 ~ 305V with linear de-rating 40 ~ 100%
Input connection Input terminal x 1 Input terminal x 1,
Bypass Input terminal x 1
Output Power Factor Unity
Voltage 200, 208, 220, 230, 240 Vac (Single phase) 380/400/415 Vac (Three phase), or
220/230/240 Vac (Single phase)
Frequency
50/60Hz ±0.05Hz
Voltage Harmonic
Distortion
≤ 2% (linear load)
Overload Capability ≤ 105%: continuous; 106 ~ 125%, 5 min.; 126 ~ 150%, 1 min.;
> 150%: 500ms
≤ 105%: continuous; 106 ~ 125%: 2 min.;
126 ~ 150%: 30 sec; > 150%: 200ms
Receptacle
Standard Runtime Model
C13x6, C19x2, Terminal x 1
Load bank: C19x1
Extended Runtime Model Terminal x 1
Load bank: Terminal x 1
C13x6, C19x4, Terminal x 1
Load bank: C19x1
Terminal x 1
Efficiency
AC-AC
ECO Mode
Up to 95.5%
Up to 99%
Battery
Standard Runtime Model
192 Vdc
192 Vdc
240 Vdc
240 Vdc
Voltage
Charger
Current
Extended Runtime Model 144 Vdc*, 192 ~ 264 Vdc
Standard Runtime Model
1A (default) 1.5A (default)
Extended Runtime Model Up to 8A
Up to 8A
Typical
Standard
75% load 7.5 min. 5.5 min. 9 min. 6 min.
Backup Time Runtime Model
(VRLA bat.)
Full load 5 min. 3 min. 5 min. 3.5 min.
Depending on different
configurations required by customers
Extended Runtime Model Depending on different configurations required by customers
Audible Noise 48 dB 50 dB 54 dB
Display
Graphical and multi-lingual LCD
Communication Interfaces MINI Slot x 1, Parallel Port** x 2, USB Port x 1, RS232 Port*** x 1, RS485 Port x 1, REPO/ROO Port x 1,
Dry Contact x 4
Dimensions
(W x D x H)
Standard Runtime Model
440 x 665 x 176 mm 440 x 750 x 218 mm
Extended Runtime Model 440 x 430 x 88.2 mm 440 x 565 x 88.2 mm
440 x 760 x 88.2 mm
22.5 kg 22.5 kg
* De-rating to 70% load
** Only applicable to RT 5-10kVA Extended Runtime Model and RT 15/20kVA
*** Not applicable to RT 20kVA
**** When the operating temperature is at 40 ~ 55° C, the UPS will be de-rated to 75% of its capacity
All specifications are subject to change without prior notice.
www.deltapowersolutions.com
Leaflet_UPS_RT5-20kVA_CE_std-ext_en-us_DAAIEI-02-JY
Model RT-5K RT-6K RT-8K RT-10K RT-15K3P RT-20K3P
Weight
Standard Runtime Model
Extended Runtime Model
54 kg 54 kg
10.9 kg 10.9 kg
85.5 kg
15.2 kg
85.5 kg
15.2 kg
Environment
Operating Temperature
Relative Humidity
0 ~ 55° C****
5 ~ 95% (non-condensing)