Page 1
www.sensata.com
Copyright © 2020 Sensata Technologies, Inc.
| IAL/CEL/LEL SERIES
HYDRAULIC MAGNETIC CIRCUIT PROTECTORS
Introduction
IAL/IUL/IEL/LEL magnetic circuit protectors provide low-cost power switching, reliable circuit protection and accurate circuit control for equipment in
the international marketplace.
IAL models are for those applications where the unit’s inherent attributes are desired, but compliance with the various standards is not required.
IUL models have been tested and approved in accordance with UL 1077
requirements for UL recognition.
IEL/LEL models are TUV approved to IEC 60947-2. They meet IEC spacing
requirements, mandatory for equipment which must comply with IEC
specifications. In addition, the IEL models are UL recognized to UL 1077
as supplementary protectors and the LEL models are UL listed under the
conditions of UL 489. Both are CSA certified and CCC Approved. The IEL
is CSA certified as a supplementary protector per CSA C22.2–No. 235.
The CEL model has achieved two new enhancements, including a single
pole, 125 amp rating with TÜV approval, and a parallel 4-pole version
with 400 amp rating.
Airpax™ IAL/CEL/LEL circuit protectors are available in a wide variety
of configurations, including series, series with auxiliary switch, shunt
and relay with choice of delays and ratings in DC and/or 50/60Hz or
400Hz versions. Single or multi-pole versions are available with a
variety of pole arrangements to meet your specifications. Please see
the appropriate product specification table for ratings and limitations.
SINGLE POLE, STANDARD STUD TERMINAL
(SEE TABLE)
(SEE TABLE)
[3.56]
.140
[3.61]
.142
[47.22]
1.859
[17.53]
.690
ON
OFF
[7.14]
.281
[49.28]
1.940
STUD TERMINAL TYPES
Screw Stud Thread Dimension “A” Dimension “B”
M6 .510 ± .045
[12.95 ± 1.14]
.652 ± .035
[16.56 ± 0.89]
1/4 -20 .545 ± .045
[13.84 ± 1.14]
.687 ± .035
[17.45 ± 0.89]
M5 .510 ± .045
[12.95 ± 1.14]
.652 ± .035
[16.56 ± 0.89]
10-32 .545 ± .045
[13.84 ± 1.14]
.687 ± .035
[17.45 ± 0.89]
Tolerance ± .015 [.39] unless noted.
Dimensions in brackets [ ] are millimeters.
www.sensata.com
Page 2
Copyright © 2020 Sensata Technologies, Inc.
[19.05]
.750
[36.53]
1.438
[63.24]
2.490
[10.21]
.402
[5.59]
.220
[52.32]
2.060
2X 6-32 THREAD
.140 [3.56] DEEP
M3 ISO THD. OPTIONAL
[7.13]
.281
[49.28]
1.940
[3.61]
.142
Screw Terminal
Single Pole
[7.13]
.281
[49.28]
1.940
[6.35]
ÿ .250 MAX.
[15.04]
.592
[9.96]
.392
[9.53]
.375
Clip Terminal
[24.57]
.967
Bullet Terminal
[19.18]
.755
[52.32]
2.060
[36.78]
1.448
[3.96]
2X ÿ .156
[10.98]
.432
Mounting Detail
Panel Mounting Detail
Tolerance ±.005 [.13] unless noted.
Notes:
A Terminal protrusion dimensions are referenced from back of mounting panel.
B Each screw terminal is supplied with a 10-32x.312 [7.92] or M5 x 8mm screw, flatwasher and external tooth lockwasher.
C Stud terminals are supplied with a flatwasher, external tooth lockwasher and a 10-32 or M5 hex nut (<=70A) (<=50A for LEL),1/4-20 or M6 hex nut
(>70A)(>50A for LEL).
Bullet terminal receptacle should be .312 ± .001 diameter hole not less than .250 depth. Contact Sensata for other bullet sizes.
Each outer terminal is supplied with a flatwasher, tooth lockwasher and a hex nut.
MULTI-POLE CIRCUIT PROTECTORS
Multi-pole units are combined in an assembly with the trip mechanisms internally coupled. A fault in any protected circuit opens all poles simultaneously.
Applications include use in polyphase circuits, single-phase three-wire systems, or in two or more related but electrically isolated circuits. A mix of
delays, ratings and configurations are offered. The auxiliary switch is offered with either gold or silver contacts and is available when a series
construction pole is specified.
An assembly consisting of two single pole units, having their trip mechanisms internally coupled, is available with either a single toggle handle
or with a handle per pole. Please see decision one of the part number decision tables. Individual poles may vary in ratings, delays and internal
configurations. If the poles are of series construction, an auxiliary switch may be included in either or both poles, allowing you to mix SELV and
hazardous voltages.
Two Pole