Data sheet | Pressure transmitters, EMP 2
IC.PD.P20.E8.02 | 520B8644 | 2© Danfoss | DCS (im) | 2018.09
Technical data
Performance (EN 60770)
Sensor temperature range
Normal -10 – 70 °C, (Ref. Fig. 1)
ATEX Zone 2 -10 – 85 °C
Transport / storage temperature -50 – 70 °C
Media temperature -40 – 100 °C, (Ref. Fig. 1)
Media
Water, fuel, oil, lubricating oil, refrigerants,
ammonia, gas etc.
Voltage supply Max. 32 V and min. 12 V d.c. between terminals N and P
Load resistance
A. max. 410 Ω at 24 V d.c. 50% / -20%
B. max. 650 Ω at 24 V d.c. 50% / 0%
Zero point adjustment - 5 – 20% range span; but max. -1–1.5 bar (kp/cm
2
)
Span adjustment ± 5% of range span; max. ± 5 bar (kp/cm
2
)
Combination of span and zero point adjustments - 5 – 20% of range span
Noise – immunity
Complies with the standard for industrial apparatus
EN 61000-6-2. The standard contains tests for the following:
HF fields, mains transmitted HF, voltage transients,
electrostatic immunity, supply voltage variations,
low-frequency radiation and transient protection in
accordance with Germanischer Lloyd
Noise – emission Complies with standard EN 61000-6-3
Accuracy
< 0.3 % of FS
In vacuum (below 0 bar) < 2.3 % of FS
Temperature dependence
Thermal zero point shift ≤ ± 0.06 % FS / °C
Thermal sensitivity (span) shift ≤ ± 0.06 % FS / °C
Voltage dependence ≤ ± 0.1% FS / 10 V
Vibration stability
3 – 30 Hz amplitude 1.13 mm and 30 – 300 Hz
acceleration 4G according to IEC 60068-2-6.
The requirements of the ship classification
societies are up to 100 Hz, acceleration 4G.
Extended specifications by prior arrangement
Time constant
Liquids with viscosity
< 100 cSt
< 4 ms
Air and gas in combination
with pulse snubber:
< 35 ms
Shock stability 500 g for 1 ms to IEC 60068-2-27
Enclosure
IP65
Housings are made of enamelled pressure-die-cast
aluminium (GD-AISI 12)
Pressure connection G ¼, G ½ A standard, G 3⁄8 A mano
Net weight approx. 1 kg
Cable entry Pg 13.5 for cable diameters 5 – 14 mm
Identification
The type designation and code number of the transmitter is embossed on the side of the housing at the
bottom close to the pressure connector.
Explosive atmospheres
Zone 2 applications EN60079-0; EN60079-15
When used in ATEX Zone 2 areas at temperatures <-10 °C the cable and plug must be protected against impact