General Description:
18 AWG solid bare copper-covered steel conductor, foam polyethylene insulation, Duobond® IV Quad
Shield (100% coverage), PVC Jacket.
Physical Characteristics (Overall)
Conductor
AWG:
# Coax AWG Stranding Conductor Material Dia. (mm)
1 18 Solid BCCS - Bare Copper Covered Steel 1.016
Total Number of Conductors: 1
Insulation
Insulation Material:
Insulation Material Dia. (mm)
Gas-injected FPE - Foam Polyethylene 4.572
Outer Shield
Outer Shield Material:
Layer # Outer Shield Trade Name Type Outer Shield Material Coverage (%)
1 Bonded Duofoil® Tape Bonded Aluminum Foil-Polyester Tape-Aluminum Foil 100
2 Braid AL - Aluminum 60
3 Duofoil® Tape Aluminum Foil-Polyester Tape-Aluminum Foil 100
4 Braid AL - Aluminum 40
Outer Jacket
Outer Jacket Material:
Outer Jacket Material
PVC - Polyvinyl Chloride
Overall Cable
Overall Nominal Diameter: 7.569 mm
Mechanical Characteristics (Overall)
Operating Temperature Range: -30°C To +75°C
Bulk Cable Weight: 49.111 Kg/Km
Max. Recommended Pulling Tension: 720.608 N
Min. Bend Radius/Minor Axis: 76.200 mm
Applicable Specifications and Agency Compliance (Overall)
Applicable Standards & Environmental Programs
NEC/(UL) Specification: CL2R, CMG, CMR
CEC/C(UL) Specification: CMG
EU Directive 2011/65/EU (ROHS II): Yes
EU CE Mark: Yes
EU Directive 2000/53/EC (ELV): Yes
EU Directive 2002/95/EC (RoHS): Yes
Page 1 of 3 01-30-2019
Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION
3092A Coax - ControlNet™ Quad Shielded Coax
EU RoHS Compliance Date (mm/dd/yyyy): 01/01/2004
EU Directive 2002/96/EC (WEEE): Yes
EU Directive 2003/11/EC (BFR): Yes
CA Prop 65 (CJ for Wire & Cable): Yes
MII Order #39 (China RoHS): Yes
RG Type: 6/U
Flame Test
UL Flame Test: UL1666 Vertical Shaft
Suitability
Sunlight Resistance: Yes
Plenum/Non-Plenum
Plenum (Y/N): No
Plenum Number: 3093A
Electrical Characteristics (Overall)
Nom. Characteristic Impedance:
Impedance (Ohm)
75
Nom. Inductance:
Inductance (µH/m)
0.318257
Nom. Capacitance Conductor to Shield:
Capacitance (pF/m)
53.1522
Nominal Velocity of Propagation:
VP (%)
82
Nominal Delay:
Delay (ns/m)
4.19968
Nom. Conductor DC Resistance:
DCR @ 20°C (Ohm/km)
91.868
Nominal Outer Shield DC Resistance:
DCR @ 20°C (Ohm/km)
11.8116
Nom. Attenuation:
Freq. (MHz) Attenuation (dB/100m)
1 1.14835
2 1.24678
5 1.47645
10 1.93579
20 2.82166
50 4.49497
100 6.46357
200 9.25242
300 11.4179
400 13.2552
Max. Operating Voltage - UL:
Voltage
300 V RMS