For more Information
please call
1-800-Belden1
General Description:
20 AWG solid TC conductors, conductors cabled, polypropylene insulation, overall Beldfoil® shield (100%
coverage), 22 AWG solid TC drain wire, HDPE jacket.
Physical Characteristics (Overall)
Conductor
AWG:
# Conductors AWG Stranding Conductor Material
10 20 Solid TC - Tinned Copper
Total Number of Conductors: 10
Insulation
Insulation Material:
Insulation Material Wall Thickness (mm)
PP - Polypropylene 0.3302
Outer Shield
Outer Shield Material:
Outer Shield Trade Name Type Outer Shield Material Coverage (%)
Beldfoil® Tape Aluminum Foil-Polyester Tape 100
Outer Shield Drain Wire AWG:
AWG Stranding Drain Wire Conductor Material
22 Solid TC - Tinned Copper
Outer Jacket
Outer Jacket Material:
Outer Jacket Material Nom. Wall Thickness (mm)
HDPE - High Density Polyethylene 1.016
Overall Cable
Overall Cabling Color Code Chart:
Color
Black
White
Red
Green
Brown
Blue
Orange
Yellow
Purple
Gray
Overall Nominal Diameter: 7.874 mm
Mechanical Characteristics (Overall)
Operating Temperature Range: -40°C To +80°C
Bulk Cable Weight: 89.292 Kg/Km
Max. Recommended Pulling Tension: 551.577 N
Page 1 of 3 01-30-2019
Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION
9890 Multi-Conductor - Direct Burial Cable
Min. Bend Radius/Minor Axis: 82.550 mm
Applicable Specifications and Agency Compliance (Overall)
Applicable Standards & Environmental Programs
EU Directive 2011/65/EU (ROHS II): Yes
EU CE Mark: Yes
EU Directive 2000/53/EC (ELV): Yes
EU Directive 2002/95/EC (RoHS): Yes
EU RoHS Compliance Date (mm/dd/yyyy): 01/01/2004
EU Directive 2002/96/EC (WEEE): Yes
EU Directive 2003/11/EC (BFR): Yes
CA Prop 65 (CJ for Wire & Cable): Yes
MII Order #39 (China RoHS): Yes
Plenum/Non-Plenum
Plenum (Y/N): No
Electrical Characteristics (Overall)
Nom. Capacitance Conductor to Conductor:
Capacitance (pF/m)
75.463
Nom. Capacitance Cond. to Other Conductor & Shield:
Capacitance (pF/m)
137.802
Nom. Conductor DC Resistance:
DCR @ 20°C (Ohm/km)
34.4505
Nominal Outer Shield DC Resistance:
DCR @ 20°C (Ohm/km)
36.091
Max. Operating Voltage - Non-UL:
Voltage
350 V RMS
Max. Recommended Current:
Current
2.7 Amps per conductor @ 25°C
Put Ups and Colors:
Item # Putup Ship Weight Color Notes Item Desc
9890 0101000 1,000 FT 65.000 LB BLACK C 10 #20 PP SHLD PE
9890 010500 500 FT 33.000 LB BLACK C 10 #20 PP SHLD PE
Notes:
C = CRATE REEL PUT-UP.
Revision Number: 2 Revision Date: 11-13-2012
© 2019 Belden, Inc
All Rights Reserved.
Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications
described herein are subject to error or omission and to change without notice, and the listing of such information and specifications does not
ensure product availability.
Belden provides the information and specifications herein on an "AS IS" basis, with no representations or warranties, whether express,
statutory or implied. In no event will Belden be liable for any damages (including consequential, indirect, incidental, special, punitive, or
exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether in an action under contract,
Page 2 of 3 01-30-2019
Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION
9890 Multi-Conductor - Direct Burial Cable