General Description:
18 AWG solid bare copper-covered steel conductor, foam polyethylene insulation, Duobond IV® quad
shield (100% coverage), PVC inner jacket, aluminum interlocked armor, PVC sunlight-resistant outer jacket.
Usage (Overall)
Suitable Applications: ControlNet™, Modbus II, Industrial Coax
Physical Characteristics (Overall)
Conductor
AWG:
# Coax AWG Stranding Conductor Material Dia. (mm)
1 18 Solid BCCS - Bare Copper Covered Steel 1.016
Total Number of Conductors: 1
Insulation
Insulation Material:
Insulation Material Dia. (mm)
FPE - Foam Polyethylene 4.572
Inner Jacket
Inner Jacket Material:
Inner Jacket Material Nom. Dia. (mm)
PVC - Polyvinyl Chloride 7.569
Outer Shield
Outer Shield Material:
Layer # Outer Shield Trade Name Type Outer Shield Material Coverage (%)
1 Bonded Duofoil® Tape Bonded Aluminum Foil-Polyester Tape-Aluminum Foil 100
2 Braid AL - Aluminum 60
3 Duofoil® Tape Aluminum Foil-Polyester Tape-Aluminum Foil 100
4 Braid AL - Aluminum 40
Outer Jacket
Outer Jacket Material:
Outer Jacket Material Nom. Wall Thickness (mm)
PVC - Polyvinyl Chloride 1.143
Armor
Armor Type: Interlocking
Armor Material: Aluminum
Diameter over Armor: .501
Overall Cable
Overall Nominal Diameter: 15.011 mm
Mechanical Characteristics (Overall)
Operating Temperature Range: -40°C To +75°C
Bulk Cable Weight: 211.324 Kg/Km
Max. Recommended Pulling Tension: 889.640 N
Page 1 of 3 01-30-2019
Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION
123092A Coax - ControlNet™ Quad Shielded Coax
Max. Recommended Pulling Tension: 889.640 N
Min. Bend Radius/Minor Axis: 180.340 mm
Applicable Specifications and Agency Compliance (Overall)
Applicable Standards & Environmental Programs
NEC/(UL) Specification: CL2, CM
EU Directive 2011/65/EU (ROHS II): Yes
EU Directive 2000/53/EC (ELV): Yes
EU Directive 2002/95/EC (RoHS): Yes
EU RoHS Compliance Date (mm/dd/yyyy): 10/01/2005
EU Directive 2002/96/EC (WEEE): Yes
EU Directive 2003/11/EC (BFR): Yes
CA Prop 65 (CJ for Wire & Cable): Yes
MII Order #39 (China RoHS): Yes
RG Type: 6/U
Flame Test
UL Flame Test: UL1685 Vertical Tray Flame Test
CSA Flame Test: FT4
Suitability
Suitability - Indoor: Yes
Suitability - Outdoor: Yes
Sunlight Resistance: Yes
Plenum/Non-Plenum
Plenum (Y/N): No
Electrical Characteristics (Overall)
Nom. Characteristic Impedance:
Impedance (Ohm)
75
Nom. Inductance:
Inductance (µH/m)
0.318257
Nom. Capacitance Conductor to Shield:
Capacitance (pF/m)
53.1522
Nominal Velocity of Propagation:
VP (%)
82
Nominal Delay:
Delay (ns/m)
4.19968
Nom. Conductor DC Resistance:
DCR @ 20°C (Ohm/km)
91.868
Nominal Outer Shield DC Resistance:
DCR @ 20°C (Ohm/km)
11.8116
Nom. Attenuation:
Freq. (MHz) Attenuation (dB/100m)
Page 2 of 3 01-30-2019
Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION