For more Information
please call
1-800-Belden1
General Description:
18 AWG triads stranded (7x26) bare copper conductors, twisted triads, PVC/Nylon insulation, individually
shielded plus an overall Beldfoil shield (100% coverage), PVC jacket.
Physical Characteristics (Overall)
Conductor
AWG:
# Triads AWG Stranding Conductor Material
4 18 7x26 BC - Bare Copper
Total Number of Conductors: 12
Insulation
Insulation Material:
Insulation Material
PVC/Nylon - Polyvinyl Chloride/Nylon
Inner Shield
Inner Shield Material:
Inner Shield Trade Name Type Inner Shield Material Coverage (%)
Beldfoil® Tape Aluminum Foil-Polyester Tape 100
Inner Shield Drain Wire AWG:
AWG
20
Inner Shield Drain Wire Stranding: 7x28
Inner Shield Drain Wire Conductor Material: TC - Tinned Copper
Inner Shield Color Code Chart:
Number Color
1 Black & White & Red and numbered 1
2 Black & White & Red and numbered 2
3 Black & White & Red and numbered 3
4 Black & White & Red and numbered 4
Outer Shield
Outer Shield Material:
Outer Shield Trade Name Type Outer Shield Material Coverage (%)
Beldfoil® Tape Aluminum Foil-Polyester Tape 100
Outer Shield Drain Wire AWG:
AWG Stranding Drain Wire Conductor Material
18 7x26 TC - Tinned Copper
Outer Jacket
Outer Jacket Material:
Outer Jacket Material Nom. Wall Thickness (mm)
PVC - Polyvinyl Chloride 1.6002
Outer Jacket Ripcord: Yes
Overall Cable
Overall Cabling Lay Length & Direction:
Page 1 of 3 01-30-2019
Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION
1093A Triad - 600V Tray Cable
Length (mm) Twists (twist/m)
177.037303 5.64332
Overall Cabling Color Code Chart:
Number Color
1 Black printed #1
2 Black printed #2
3 Black printed #3
4 Black printed #4
Overall Nominal Diameter: 14.656 mm
Pair
Pair Lay Length & Direction:
Lay Length (mm) Twists (twist/m)
63.5 15.749
Mechanical Characteristics (Overall)
Wet Temperature Range: -30°C To +75°C
Dry Temperature Range: -30°C To +90°C
Bulk Cable Weight: 268.322 Kg/Km
Max. Recommended Pulling Tension: 1543.530 N
Min. Bend Radius/Minor Axis: 152.400 mm
Applicable Specifications and Agency Compliance (Overall)
Applicable Standards & Environmental Programs
NEC/(UL) Specification: NPLF, TC-ER
EU Directive 2011/65/EU (ROHS II): Yes
EU CE Mark: Yes
EU Directive 2000/53/EC (ELV): Yes
EU Directive 2002/95/EC (RoHS): Yes
EU RoHS Compliance Date (mm/dd/yyyy): 04/01/2005
EU Directive 2002/96/EC (WEEE): Yes
EU Directive 2003/11/EC (BFR): Yes
CA Prop 65 (CJ for Wire & Cable): Yes
MII Order #39 (China RoHS): Yes
Other Specification: ICEA S-73-532, S-61-402
Flame Test
UL Flame Test: UL1685 UL Loading
C(UL) Flame Test: FT4
IEEE Flame Test: 1202
Suitability
Suitability - Burial: Yes
Sunlight Resistance: Yes
Plenum/Non-Plenum
Plenum (Y/N): No
Electrical Characteristics (Overall)
Nom. Capacitance Conductor to Shield:
Description Capacitance (pF/m)
Individual 141.083
Page 2 of 3 01-30-2019
Detailed Specifications & Technical Data
METRIC MEASUREMENT VERSION
1093A Triad - 600V Tray Cable