FEATURES BENEFITS
Capability to clamp and withstand high-energy transients
Ensures low-residual voltage during high-energy surge events and higher nominal discharge current
to prevent disruption, downtime, and degradation or damage to equipment
UL and VDE-IEC compliant in single part number One component can be utilized globally, reducing inventory needs and simplifying allocation of parts
Interlocking tab mechanism Secures module to withstand vibration
No additional overcurrent protection devices required in UL applications Reduces the number of components and costs required for protection
SPD type and voltage-coded plug-in module
Prevents specific SPD/voltage module from being plugged into wrong base. Eliminates risk of
improper protection
Compact footprint Increases panel design flexibility
Visual life indicator Quick visual determines module replacement status to avoid loss of protection
Pluggable module Fast and simple to replace, minimizing maintenance and downtime. No tools required
Thermal protection Eliminates catastrophic failure
IP20 protection rating Finger-safe design increases worker protection
Littelfuse SPD2 Series Type 2 Surge Protection Devices (SPDs) for branch circuits safeguard components from transient overvoltage or surges
by limiting the fault current to a load or the unit being protected. Surges may be caused by an indirect lightning strike but, the majority—sixty to
eighty percent
1
—are caused by equipment being turned on or off within a facility. These surges damage components costing money to repair or
replace as well as create unplanned downtime resulting in unfulfilled orders, missed deadlines, unreliable systems and/or dangerous situations.
The DIN-rail mounted SPDs are available in a wide range of operating voltages and include solar applications. They are ideal for:
Power Distribution
Load Centers
Transformers
Generators
HVAC or Medical
Equipment
[1] National Electrical Safety Month 2015, Electrical Safety Foundation International Surge and Protect.
Available: https://www.esfi.org/resource/surge-and-protect-413
Computers and Communications
LANs
WANs
Intercoms
Fire, Security, UPS or Building
Management Systems
Industrial Controls
Programmable Logic Controllers
Motor Controls
Variable-Frequency Drives
Proximity Sensors
Barcoding Equipment
Machine Vision Systems
Electrical Loads
Motors
Fans
Heaters
Blowers
Ballasts
www.Littlefuse.com/SPD
SURGE A PATH
TO PROTECTION
SPD2
Series
IEC Module & Base Ordering Information
SPD2 Series
(XP+0)
Ordering
Number
IEC Electrical Specifications
Nominal
AC
Voltage
(50/60 Hz)
(Uo/Un)
Maximum
Continuous
Operating
AC Voltage
(Uc)
Nominal
Discharge
Current
(8/20 μs)
(In)
Maximum
Discharge
Current
(8/20 μs)
(Imax)
Voltage
Protection
Level
(Up)
Short-Circuit
AC
Current
Rating
(ISCCR)
TOV
Withstand
5 s
(UT)
TOV
120 min
(UT) /
Mode
SPD2-075-1P0-R 60 V 75 V 20 kA 50 kA 800 V 25 kA / 50 kA 114 V 114 V / Withstand
SPD2-150-1P0-R 120 V 150 V 20 kA 50 kA 1250 V 25 kA / 50 kA 229 V 229 V / Withstand
SPD2-300-1P0-R 240 V 300 V 20 kA 50 kA 1500 V 25 kA / 50 kA 337 V 442 V / Safe Fail
SPD2-350-1P0-R 277 V 350 V 20 kA 50 kA 1750 V 25 kA / 50 kA 403 V 529 V / Safe Fail
SPD2-480-1P0-R 400 V 480 V 20 kA 50 kA 2300 V 25 kA / 50 kA 581 V 762 V / Safe Fail
SPD2-550-1P0-R* 480 V 550 V 20 kA 50 kA 2500 V 25 kA / 50 kA 697 V 915 V / Safe Fail
SPD2-750-1P0-R 600 V 750 V 20 kA 35 kA 3400 V 25 kA / 50 kA 871 V 1143 V / Safe Fail
SPD2-150-2P0-R 120 V 150 V 20 kA 50 kA 1250 V 25 kA / 50 kA 229 V 229 V / Withstand
SPD2-300-2P0-R 240 V 300 V 20 kA 50 kA 1500 V 25 kA / 50 kA 337 V 442 V / Safe Fail
SPD2-350-2P0-R 277 V 350 V 20 kA 50 kA 1750 V 25 kA / 50 kA 403 V 529 V / Safe Fail
SPD2-480-2P0-R 400 V 480 V 20 kA 50 kA 2300 V 25 kA / 50 kA 581 V 762 V / Safe Fail
SPD2-550-2P0-R* 480 V 550 V 20 kA 50 kA 2500 V 25 kA / 50 kA 697 V 915 V / Safe Fail
SPD2-750-2P0-R 600 V 750 V 20 kA 35 kA 3400 V 25 kA / 50 kA 871 V 1143 V / Safe Fail
SPD2-150-3P0-R 120 V 150 V 20 kA 50 kA 1250 V 25 kA / 50 kA 229 V 229 V / Withstand
SPD2-300-3P0-R 240 V 300 V 20 kA 50 kA 1500 V 25 kA / 50 kA 337 V 442 V / Safe Fail
SPD2-350-3P0-R 277 V 350 V 20 kA 50 kA 1750 V 25 kA / 50 kA 403 V 529 V / Safe Fail
SPD2-480-3P0-R 400 V 480 V 20 kA 50 kA 2300 V 25 kA / 50 kA 581 V 762 V / Safe Fail
SPD2-550-3P0-R* 480 V 550 V 20 kA 50 kA 2500 V 25 kA / 50 kA 697 V 915 V / Safe Fail
SPD2-750-3P0-R 600 V 750 V 20 kA 35 kA 3400 V 25 kA / 50 kA 871 V 1143 V / Safe Fail
SPD2-150-4P0-R 120 V 150 V 20 kA 50 kA 1250 V 25 kA / 50 kA 229 V 229 V / Withstand
SPD2-300-4P0-R 240 V 300 V 20 kA 50 kA 1500 V 25 kA / 50 kA 337 V 442 V / Safe Fail
SPD2-350-4P0-R 277 V 350 V 20 kA 50 kA 1750 V 25 kA / 50 kA 403 V 529 V / Safe Fail
SPD2-480-4P0-R 400 V 480 V 20 kA 50 kA 2300 V 25 kA / 50 kA 581 V 762 V / Safe Fail
SPD2-550-4P0-R* 480 V 550 V 20 kA 50 kA 2500 V 25 kA / 50 kA 697 V 915 V / Safe Fail
*Products are UL Listed only
SPD2 Series
(XP+1)
Ordering
Number
IEC Electrical Specifications
Nominal
AC Voltage
(50/60 Hz)
(Uo/Un)
Maximum
Continuous
Operating
AC Voltage
(L-N / N-PE UC)
Nominal
Discharge
Current
(8/20 μs)
(L-N /
N-PE In)
Maximum
Discharge
Current
(8/20 μs)
(L-N / N-PE
Imax)
Voltage
Protection
Level
(L-N / N-PE Up)
Follow
Current
Interrupt
Rating
(N-PE In)
Short-Circuit
AC
Current
Rating
(L-N ISCCR)
TOV
Withstand
5 s
(L-N UT)
TOV
120 min
(L-N UT) / Mode
TOV
Withstand
200 ms
(N-PE UT)
SPD2-075-1P1-R
60 V 75 V / 305 V
20 kA / 40 kA 50 kA / 65 kA 800 V / 1500 V 100 ARMS 25 kA / 50 kA 114 V 114 V / Withstand 1200 V
SPD2-150-1P1-R
120 V 150 V / 305 V
20 kA / 40 kA 50 kA / 65 kA 1250 V / 1500 V 100 ARMS 25 kA / 50 kA 229 V 229 V / Withstand 1200 V
SPD2-300-1P1-R
240 V 300 V / 305 V
20 kA / 40 kA 50 kA / 65 kA 1500 V / 1500 V 100 ARMS 25 kA / 50 kA 337 V 442 V / Safe Fail 1200 V
SPD2-350-1P1-R
277 V 350 V / 305 V
20 kA / 40 kA 50 kA / 65 kA 1750 V / 1500 V 100 ARMS 25 kA / 50 kA 403 V 529 V / Safe Fail 1200 V
SPD2-300-3P1-R
240 V 300 V / 305 V
20 kA / 40 kA 50 kA / 65 kA 1500 V / 1500 V 100 ARMS 25 kA / 50 kA 337 V 442 V / Safe Fail 1200 V
SPD2-350-3P1-R
277 V 350 V / 305 V
20 kA / 40 kA 50 kA / 65 kA 1750 V / 1500 V 100 ARMS 25 kA / 50 kA 403 V 529 V / Safe Fail 1200 V
SPD2 PV
Series
Ordering
Number
IEC Electrical Specifications
Maximum Continuous
Operatins DC Voltage
(UCPV)
Nominal
Discharge Current
(8/20 μs)
(In)
Maximum
Discharge Current
(8/20 μs)
(Imax)
Total
Discharge Current
(ITOTAL)
Voltage
Protection Level
(Up)
Short-Circuit
Current
Rating
(ISCPV)
SPD2-PV11-3P0-R 1100 V 20 kA 40 kA 50 kA 3800 V 11 kA
SPD2-PV15-3P0-R 1500 V 20 kA 30 kA 40 kA 5000 V 11 kA
©2019 Littelfuse Protection Relays & Controls www.Littlefuse.com/SPD
For IEC product weight, refer to corresponding product number on UL chart.
Module & Base Part Numbering Systems
SPD2 VVV XPZ R
Module & Base
Series
Neutral
Number of Poles
Maximum Continuous
Operating AC Voltage
(1=yes or 0=no)
SPD2 PV VV XPZ R
Optional Remote Contact
Series
Number of Poles
Photovoltaic
Maximum Continuous Operating
DC Voltage in Hundreds
Neutral