• DXM Wireless Controller Sell Sheet, p/n
194063
• DXM100-B1 Wireless Controller Datasheet, p/n
186724
• DXM100-B2 Wireless Controller Datasheet, p/n
195232
• DXM100-Bx Wireless Controller Instruction Manual, p/n
190037
• DXM100-S1 Wireless Modbus Slave Datasheet, p/n
195454
• DXM100-S2 Wireless Modbus Slave Datasheet, p/n
195231
• DXM100-Sx Wireless Modbus Slave Instruction Manual, p/n
188231
• DXM ScriptBasic Instruction Manual, p/n
191745
• DXM Controller Configuration Quick Start, p/n
191247
• DXM Configuration Tool
software
• DXM Configuration Tool Instruction Manual, p/n
158447
• DXM EDS
Configuration file
• Tech Note:
Activating and Provisioning Cellular Service
• Additional technical notes and videos
Technical notes, configuration examples, and ScriptBasic program examples are available at
www.bannerengineering.com
.
DXM100-S1 Modbus Slave System Overview
Banner's DXM Logic Controller integrates Banner's wireless radio and local I/O for a remote I/O device.
Connectivity
Sure Cross Radios
RS-485 Master
I/O
Universal Inputs
Discrete Outputs
Courtesy Power
Switch Power
Inputs/Outputs—On-board universal and programmable I/O
ports connect to local sensors, indicators, and control
equipment.
• Universal Inputs
• Discrete outputs
• Courtesy power
��� Switch power
• Battery backup
• Solar controller
Connectivity—The integrated Sure Cross
®
wireless radio enables Modbus connectivity to remote sensors, indicators, and control
equipment.
Wired Connectivity
Field Bus: Modbus RS-485 Master
Wireless Connectivity
Sure Cross MultiHop 900 MHz, or MultiHop 2.4 GHz
Specifications
MultiHop Radio Specifications
Radio Range
1
900 MHz, 1 Watt: Up to 9.6 km (6 miles)
2.4 GHz, 65 mW: Up to 3.2 km (2 miles)
Antenna Minimum Separation Distance
900 MHz, 150 mW and 250 mW: 2 m (6 ft)
900 MHz, 1 Watt: 4.57 m (15 ft)
2.4 GHz, 65 mW: 0.3 m (1 ft)
Radio Transmit Power
900 MHz, 1 Watt: 30 dBm (1 W) conducted (up to 36 dBm EIRP)
2.4 GHz, 65 mW: 18 dBm (65 mW) conducted, less than or equal to 20 dBm
(100 mW) EIRP
Spread Spectrum Technology
FHSS (Frequency Hopping Spread Spectrum)
900 MHz Compliance (1 Watt)
FCC ID UE3RM1809: This device complies with FCC Part 15, Subpart C,
15.247
IC: 7044A-RM1809
2.4 GHz Compliance (MultiHop)
FCC ID UE300DX80-2400 - This device complies with FCC Part 15, Subpart
C, 15.247
ETSI EN 300 328: V1.8.1 (2012-04)
IC: 7044A-DX8024
Antenna Connection
Ext. Reverse Polarity SMA, 50 Ohms
Max Tightening Torque: 0.45 N·m (4 lbf·in)
Packet Size (MultiHop)
900 MHz: 175 bytes (85 Modbus registers)
2.4 GHz: 75 bytes (37 Modbus registers)
1
Radio range is with the 2 dB antenna that ships with the product. High-gain antennas are available, but the range depends on the environment and line of sight. Always verify your wireless
network's range by performing a Site Survey.
Sure Cross
®
DXM100-S1 Wireless Modbus Slave
2 www.bannerengineering.com - Tel: +1-763-544-3164 P/N 195454 Rev. C