Release date 2018-07-24 14:31 Date of issue 2018-07-24 315318_eng.xml
Technical data HiC2441
2
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
Pepperl+Fuchs Group USA: +1 330 486 0002 Singapore: +65 6779 9091Germany: +49 621 776 2222
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com
General specifications
Signal type Universal
Functional safety related parameters
Safety Integrity Level (SIL) SIL 2
Supply
Connection SL1: 1a(-), 1b(-); 2a(+), 2b(+)
Rated voltage U
r
19 ... 30 V DC via Termination Board
Ripple ≤ 10 %
Rated current I
r
≤ 30 mA
Power consumption ≤ 700 mW
Analog input
Suitable field devices 2-wire SMART transmitters, current sources
Signal 0/4 ... 20 mA , limited to approx. 40 mA (depends on control system) , reverse polarity protected
Field circuit SL2: 5a(+), 5b(-) (2-wire SMART transmitter)
SL2: 5a(+), 1b(-) (2-wire SMART transmitter with current source)
Voltage drop approx. 4 V (current source)
Control circuit SL1: 8a(+), 7a(-)
Supply voltage ≥ 16 V at 20 mA (2-wire SMART transmitter)
Voltage 15 ... 30 V
Signal 0/4 ... 20 mA , sink mode , working voltage 15 ... 30 V
Ripple 20 mV
rms
Analog output
Suitable field devices I/P converters (positioner), on-site-displays
Signal 0/4 ... 20 mA
Field circuit SL2: 5a(+), 5b(-)
Load 0 ... 650 Ω
Voltage ≥ 13 V at 20 mA
Ripple 20 mV
rms
Control circuit SL1: 8a(+), 7a(-)
Voltage 12 ... 30 V
Signal 0/4 ... 20 mA
Line fault detection > 100 kΩ at max. 30 V, with field wiring open
Digital input
Field circuit SL2: 5a(+), 1a(-) (NAMUR sensor)
SL2: 5a(+), 5b(-) (dry contact)
Suitable field devices NAMUR sensors according to IEC/EN 60947-5-6, dry contacts
Signal 0.1 ... 9 mA , sink mode
Open loop voltage approx. 10 V DC , 1 kΩ series resistance
Signal 0.1 ... 9 mA
Control circuit SL1: 8a(+), 7a(-)
Voltage 13 ... 30 V
Digital output
Field circuit SL2: 5a(+), 5b(-)
Suitable field devices solenoid valves, acoustic or visual alarms
Drive capability 12 V / 40 mA at 300 Ω load
Open loop voltage U
s
approx. 22 V
Current limit I
max
45 mA
Internal resistor R
i
≥ 240 Ω
Control circuit SL1: 8a(+), 7a(-)
Voltage 1-signal: 19 ... 30 V DC
0-signal: 0 ... 5 V DC
Current 1-signal: 0 ... 45 mA, depending on the output load
0-signal: < 0.1 mA, independent of the output load
Power dissipation 1.1 W at 24 V, 300 Ω load (digital output)
Transfer characteristics
Deviation at 20 °C (68 °F)
≤ ±20 µA incl. linearity, hysteresis and supply fluctuations at 4 ... 20 mA (analog input, analog output)
≤ ±60 µA incl. linearity, hysteresis and supply fluctuations at 0 ... 45 mA (digital output)
Influence of ambient temperature < 2 µA/K (0 ... 70 °C (32 ... 158 °F))
< 3 µA/K (-40 ... 0 °C (-40 ... 32 °F))
Switching frequency ≤ 500 Hz with 50 % duty cycle (digital input, NAMUR sensor)
≤ 5 Hz (digital input, dry contact)
≤ 20 Hz (digital output)
Frequency range HART: bandwidth by 0.5 V
pp
signal and/or 1 mA
pp
signal 950 ... 2500 Hz (analog input, analog output)
Settling time ≤ 20 ms (analog input, analog output)
≤ 1 ms (digital input, NAMUR sensor)