Instruction Manual
Marking
Power supply module KLD2-FBPS-1.25.360
Statement of conformity:
TÜV 06 ATEX 553079 X
II 3G Ex ec IIC T4 Gc
Power supply module KLD2-FBPS-1.12.220
Statement of conformity:
TÜV 06 ATEX 553079 X
II 3G Ex ec IIC T4 Gc
table 1
Pepperl+Fuchs GmbH
Lilienthalstraße 200, 68307 Mannheim, Germany
table 2
Validity
Specific processes and instructions in this instruction manual require
special provisions to guarantee the safety of the operating personnel.
Target Group, Personnel
Responsibility for planning, assembly, commissioning, operation,
maintenance, and dismounting lies with the plant operator.
The personnel must be appropriately trained and qualified in order to carry
out mounting, installation, commissioning, operation, maintenance, and
dismounting of the device. The trained and qualified personnel must have
read and understood the instruction manual.
Prior to using the product make yourself familiar with it. Read the
instruction manual carefully.
Reference to Further Documentation
Observe laws, standards, and directives applicable to the intended use
and the operating location. Observe Directive 1999/92/EC in relation to
hazardous areas.
The corresponding datasheets, manuals, declarations of conformity, EU-
type examination certificates, certificates, and control drawings if
applicable supplement this document. You can find this information under
www.pepperl-fuchs.com.
Due to constant revisions, documentation is subject to permanent change.
Please refer only to the most up-to-date version, which can be found under
www.pepperl-fuchs.com.
Intended Use
The device is a power supply module designed for powering
FOUNDATION Fieldbus H1 segments in accordance with
IEC/EN 61158-2.
The device must only be operated in the specified ambient temperature
range and at the specified relative humidity without condensation.
The device is an electrical apparatus for hazardous areas of Zone 2.
The device is designed for mounting on a 35 mm DIN mounting rail
according to EN 60715.
Improper Use
Protection of the personnel and the plant is not ensured if the device is not
used according to its intended use.
Mounting and Installation
Prior to mounting, installation, and commissioning of the device you
should make yourself familiar with the device and carefully read the
instruction manual.
Do not mount a damaged or polluted device.
Do not mount the device at locations where an aggressive atmosphere
may be present.
The device must be installed and operated only in an environment that
ensures a pollution degree 2 (or better) according to IEC/EN 60664-1.
If used in areas with higher pollution degree, the device needs to be
protected accordingly.
Hazardous Area
If the device has already been operated in general electrical installations,
the device may subsequently no longer be installed in electrical
installations used in combination with hazardous areas.
Observe the installation instructions according to IEC/EN 60079-14.
Observe the installation instructions according to IEC/EN 60079-25.
Gas
The device may be installed in gas groups IIC, IIB, and IIA.
Zone 2
The device may be installed in Zone 2.
Connection or disconnection of energized non-intrinsically safe circuits is
only permitted in the absence of a potentially explosive atmosphere.
Housings and Surrounding Enclosures
The device must be installed and operated only in surrounding enclosures
that
l
comply with the requirements for surrounding enclosures according to
IEC/EN 60079-0,
l
are rated with the degree of protection IP54 according to IEC/EN 60529.
Operation, Maintenance, Repair
Do not repair, modify, or manipulate the device.
Do not use a damaged or polluted device.
If there is a defect, always replace the device with an original device.
Delivery, Transport, Disposal
Check the packaging and contents for damage.
Check if you have received every item and if the items received are the
ones you ordered.
Keep the original packaging. Always store and transport the device in the
original packaging.
Store the device in a clean and dry environment. The permitted ambient
conditions must be considered, see datasheet.
Disposing of device, packaging, and possibly contained batteries must be
in compliance with the applicable laws and guidelines of the respective
country.
DOCT-4969 / 2016-07 1 / 1