AS-i / IO-Link Module,
IO-Link Master with 4 IO-Link Ports
Bihl+Wiedemann GmbH · Floßwörthstr. 41 · D-68199 Mannheim · Phone: (+49) 621/33996-0 · Fax: (+49) 621/3392239 · eMail: mail@bihl-wiedemann.de
www.bihl-wiedemann.de We reserve the right to change any data Mannheim, 1.8.17 page 1
AS-i/IO-Link Module,
IO-Link Master with 4 IO-Link ports
fourfold IO-Link Master
2 single slaves in one housing
Power supply of IO-Link ports out of AUX (or AS-i)
(Figure similar)
Figure Type Inputs
digital
Outputs
digital
M12
wiring
(1)
(1)
M12 wiring
Port Class A: In this type Pin2 is assigned with an additional digital input.
Port Class B: This type provides an additional power supply and is suitable for the connection of devices that have an increased power
demand. In this case, pins2 and 5 are used to provide the additional power supply.
Input voltage
(sensor
supply)
(2)
(2)
Input voltage (sensor supply)
Inputs are supplied by AS-i or by AUX (auxiliary 24 V power). If supplied by AS-i, inputs can neither be connected to earth nor to external
potential.
Output voltage
(actuator
supply)
(3)
(3)
Output voltage (actuator supply)
The supply of the outputs is made by AS-i or by AUX (auxiliary 24 V power). By supply out of AS-i there is no connection to earth or exter-
nal potential allowed.
AS-i
connection
(4)
(4)
AS-i connection
The connection to AS-i as well to AUX (auxiliary 24 V power) is made via yellow or black AS-i profile cable with piercing technology or via
M12 socket (in IP20 via clamps).
AS-i
address
(5)
(5)
AS-i address
AB slave (max. 62 AB slaves/AS-i network), 2 AB slaves (max. 31 modules with 2 AB slaves), single slaves (max. 31 single slaves/AS-i
network), mixed use allowed (upon request, slaves are available with specific AS-slave profiles).
Max.
output
current
Art. no.
IP67
8x M12
4 x IO-Link port
+
4 x electronic
4x
IO-Link port
IO-Link port
class A
out of AUX out of AUX
AS-i
profile cable
2 single
slaves
500 mA BWU2853
IP67
8x M12
4 x IO-Link port
+
4 x electronic
4x
IO-Link port
IO-Link port
class A
out of AS-i out of AS-i
AS-i
profile cable
2 single
slaves
120 mA
BWU2945
(6)
(6)
Only on request.
IP67
8x M12
4 x IO-Link port
4x
IO-Link port
IO-Link port
Class B
out of AS-i
output voltage
out of AS-i;
actuator supply
out of AUX
AS-i
profile cable
2 single
slaves
120 mA BWU3020
AS-i / IO-Link Module,
IO-Link Master with 4 IO-Link Ports
Bihl+Wiedemann GmbH · Floßwörthstr. 41 · D-68199 Mannheim · Phone: (+49) 621/33996-0 · Fax: (+49) 621/3392239 · eMail: mail@bihl-wiedemann.de
page 2 Mannheim, 1.8.17 We reserve the right to change any data www.bihl-wiedemann.de
Article no. BWU2853 BWU3020
Connection
AS-i/AUX connection profile cable and piercing
Periphery connection M12
Length of connector cable I/O: max. 20 m
IO-Link
Number 4 ports Class A 4 ports Class B
Data rate COM1 / COM2 / COM3
IO-Link revision 1.1
AS-i
Profile slave 1: S-7.5.5 (ID1=F default)
slave 2: S-7.5.5 (ID1=E default)
Address 2 single slaves
Operating voltage 30 V (18 … 31.6 V)
Required master profile M4
Since AS-i specification 3.0
Max. current consumption 50 mA 200 mA
Max. current consumption
without
sensor / actuator supply
50 mA 80 mA
AUX
Voltage 24V (18…30V)
Max. current consumption 4 A
(1)
Input
Number 4 (via IO-Link port) +
4 x electronic
4 (via IO-Link port)
Power supply out of AUX out of AS-i
Supply of attached
sensors
up to
+25 °C
500 mA per port,
(sensors + outputs) max. 1000 mA
(2)
(sensors + outputs) max. 120 mA
(5)
at +40 °C 500 mA per port,
(sensors + outputs) max. 833 mA
(2)
at +55 °C 500 mA per port,
(sensors + outputs) max. 666 mA
(2)
(sensors + outputs) max. 100 mA
(5)
at +70 °C 500 mA per port,
(sensors + outputs) max. 500 mA
(2)
(sensors + outputs) max. 80 mA
(5)
Switching threshold U<5 V (low)
U>15 V (high)
Output
Number 4 (via IO-Link port)
Power supply out of AUX output voltage out of AS-i;
actuator supply out of AUX
Max.
output current
up to
+25 °C
500 mA per port,
(sensors + outputs) max. 1000 mA
(2)
(sensors + outputs) max. 120 mA
(5)
at +40 °C 500 mA per port,
(sensors + outputs) max. 833 mA
(2)
at +55 °C 500 mA per port,
(sensors + outputs) max. 666 mA
(2)
(sensors + outputs) max. 100 mA
(5)
at +70 °C 500 mA per port,
(sensors + outputs) max. 500 mA
(2)
(sensors + outputs) max. 80 mA
(5)